| Plan Review Notes For Permit 17110631 |
| Permit Number |
17110631 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-18 11:44:22 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110631 | | | 12/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED MECHANICAL PLAN IS ONE PART OF A | | | LARGER PLAN FOR INTERIOR RENOVATIONS, OR A TENANT | | | BUILD-OUT AT SUITE 215. ALL WORK AT THAT SUITE HAS BEEN | | | STOPPED UNDER A VIOLATION FOR WORK COMMENCING BEFORE | | | PERMIT. THEREFORE A THOROUGH REVIEW OF THE MECHANICAL | | | PLANS CANNOT BE PERFORMED AT THIS TIME UNTIL COMPLETE | | | ARCHITECTURAL AND MEP PLANS HAVE BEEN SUBMITTED THAT | | | CLARIFY THE USE AND OCCUPANCY OF THE SPACE. THE CURRENT | | | PLAN IS INDICATING PRESSURIZED "CLEAN ROOMS" WITH HEPA | | | FILTERING WHICH IS TYPICALLY FOUND IN MEDICAL OR | | | PHARMACEUTICAL PROCESSING FACILITIES. | | | | | | 2) CLARIFY HOW THE PRESSURIZATIONS AND HEPA FILTERING | | | SYSTEMS FOR THE ROOMS WAS ESTABLISHED- UNDER WHICH | | | DESIGN PARAMETERS, CRITERIA, CODE OR STANDARD, AND | | | PROVIDE A SUPPLEMENTAL TABLE THAT INDICATES THE | | | PRESSURE RELATIONSHIPS AND REQUIRED AIR CHANGES PER | | | HOUR FOR EACH ROOM. | | | | | | 3) THE 1/4"=1'0" SCALE DOES NOT MATCH THE PLAN. PLEASE | | | PROVIDE AN ACCURATELY SCALED PLAN- SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|