Plan Review Notes
Plan Review Notes For Permit 17110550
Permit Number 17110550
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-11-16 13:20:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN INDICATES 48 NEW FLEXHEAD
 SYSTEMS. THE ORIGINAL DESIGN DID NOT INCLUDE FLEX
 HEADS. DUE TO THE INCREASED FRICTION LOSS WITH FLEXHEAD
 SYSTEMS ARE REVIEW AND REVISED HYDRALIC CALCULATION
 SHEET SHLL BE PROVIDED TO ENSURE ADAQUATE WATER SUPPLY.
  
 PLEASE PROVIDE OR CORRECT INSTALL EQUIPMENT.
  
  