| 2017-12-08 13:49:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FEEDER "F-4" SHOWS 2/0 WIRE FEEDING A 200 AMP PANEL, |
| | PANEL A. THIS IS LABELED AS PANEL B IN THE PANEL |
| | SCHEDULE FOR PANEL DP AND SHOWS 3/0 WIRE FEEDING THE |
| | PANEL. CORRECT DISCREPANCY. BE ADVISED THAT 2/0 WIRE IS |
| | NOT RATED FOR A 200 AMP FEED. TABLE 310.15(B)(7) IS NOT |
| | PERMITTED TO BE USED UNLESS THE FEEDER IN QUESTION |
| | CARRIES 100% OF THE LOAD. PROVIDE CORRECTION. NEC |
| | 310.15(B)(7) AND (B)(15); FBC RE TABLE E3603.1, 3704.1 |
| | 2. FEEDER FROM METER CAN TO ATS SHOULD NOT INCLUDE AN |
| | EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC |
| | 250.6, 250.24 |
| | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 4. SHEET E-0, ARC FAULT BREAKER NOTE # 2 REFERENCES NEC |
| | 406.11, WHICH IS NOT THE CURRENT CODE FOR TAMPER |
| | RESISTANT RECEPTACLES. THE STATEMENT ALSO LEAVES OUT |
| | THE REQUIREMENT FOR 15 AMP RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 5. PANEL SCHEDULE FOR PANEL DP SHOWS # 1 WIRE ON A 150 |
| | AMP BREAKER FOR THE GUEST HOUSE. PROVIDE CORRECTION, |
| | SAME REASONING AS COMMENT # 1. NEC 310.15(B)(7) AND |
| | (B)(15); FBC RE TABLE E3603.1, 3704.1 |
| | 6. SECOND FLOOR PLAN SHOWS A PENDANT LIGHT IN HER |
| | CLOSET. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY |
| | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE |
| | CORRECTION. NEC 410.16; FBC RE4003.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |