2017-11-16 09:56:271) SHOW THE LENGTH & DIAMETER OF THE EARTH AUGERS USED
 TO ANCHOR THE LP TANKS ON THE PLANS. ALSO, NOTE ON THE
 PLANS HOW MANY AUGERS WILL BE USED FOR EACH TANK.
 2) SHOW THE SIZE OF THE CABLE BEING USED TO SECURE THE
 LP TANKS.
 3) SHOW ON THE PLANS THE TYPE OF FOUNDATION THAT THE LP
 TANKS WILL BE SET UPON.
 4) NOTE ON THE PLAN THE TOTAL BTU LOAD THAT WILL BE ON
 THIS SYSTEM.
 5) INDICATE ON THE PLANS HOW THE LP TANKS WILL BE
 PROTECTED FROM PHYSICAL DAMAGE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW