Plan Review Notes
Plan Review Notes For Permit 17110534
Permit Number 17110534
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-28 10:45:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110534
 11/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2, A-1, & A-2: PLEASE CLARIFY HOW THE FIRE
 DAMPERS ARE BEING INSTALLED ON THE NORTH-SIDE TENANT
 SEPARATION WALL. DETAIL 3/A-2 DOES NOT INDICATE THE
 SEPARATION WALL IS FIRE-RATED, AND SHOWS IT TERMINATING
 BELOW THE CEILING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  