2017-11-21 17:21:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110531
 11/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1. KEYNOTE #8: CORRIDORS SHALL NOT BE USED
 AS A RETURN DUCT- SEE SECTION 601.2. IF THE GRILL IS
 TRANSFERRING AIR INTO A RETURN AIR PLENUM ABOVE THE
 CORRIDOR CEILING IT IS PERMITTED - SEE SECTION 601.2.1
 (1-5.).
  