| 2018-01-18 18:28:49 | 01/18/18 RESPONDE E-MAIL TO ROY STEPHEN (ARCHITECT): |
| | |
| | GOOD EVENING MR. ROY, |
| | IF YOU HAVE NOTICED, I HAVE MADE MY COMMENT BASED ON |
| | THE INFORMATION THAT WAS SUBMITTED AT TIME OF PERMIT |
| | APPLICATION. I DIDN'T SEE ANY PROPERTY APPRAISAL IN THE |
| | SUBMITTAL. THEREFORE, BASED ON THE INFORMATION OBTAINED |
| | FROM PALM BEACH COUNTY PROPERTY APPRAISER, THE VALUE OF |
| | THE STRUCTURE IS $142,509. THAT'S WHY I MADE THE CALL |
| | FOR THE SUBSTANTIAL IMPROVEMENT. BASED ON THE 50% RULE. |
| | NOW, BASED ON THE INFORMATION YOU PROVIDED NOW IT LOOKS |
| | LIKE THE "SUBSTANTIAL IMPROVEMENT" MAY NOT APPLY IN |
| | THIS CASE. |
| | THERE ARE TWO THINGS THAT NEED TO BE ADDRESSED: |
| | FIRST, ACCORDING TO THE CITY REVISED ORDINANCE THE |
| | "APPRAISAL ANALYSES USED TO ESTABLISH MARKET VALUE |
| | SHALL HAVE BEEN PERFORMED NO MORE THAN SIX MONTHS PRIOR |
| | TO THE DATE A PERMIT APPLICATION IS SUBMITTED FOR THE |
| | PROPOSED IMPROVEMENT". SEE DEFINITION OF MARKET VALUE |
| | ON SEC. 18-289 OF ORDINANCE NO. 4729-17. THEREFORE, |
| | NEED TO PROVIDE CURRENT MARKET VALUE ANALYSIS. |
| | SECOND, THE VALUE SHOWN ON THE PERMIT APPLICATION |
| | SUBMITTED DOESN'T MATCH THE VALUE OF THE CONSTRUCTION |
| | BUDGET SUBMITTED NOW. THE VALUE NEED TO BE REVISED ON |
| | THE PERMIT APPLICATION AND NEED TO ADD YOUR DESIGN |
| | PROFESSIONAL FEES AS WELL. THE VALUE IS TO INCLUDE ALL |
| | LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND |
| | ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 |
| | CITY AMENDMENTS. |
| | WE NEED ALL THIS INFORMATION UPDATED SO OUR RECORDS |
| | REFLECT WHY THE PROPOSED IMPROVEMENTS DON'T TRIGGER THE |
| | SUBSTANTIAL IMPROVEMENT COMPLIANCE AT HIS TIME. |
| | IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT |
| | ME. |
| | REGARDS, |
| | |
| | JULIO C. GOMEZ |
| | CITY OF WEST PALM BEACH |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROPOSED SCOPE OF WORK IS CONSIDERED "SUBSTANTIAL |
| | IMPROVEMENT". BASED ON THE PALM BEACH COUNTY PROPERTY |
| | APPRAISER VALUE OF THE STRUCTURE, THE PROPOSED WORK |
| | EXCEEDS THE 50 PERCENT THE VALUE OF THIS STRUCTURE. |
| | EXISTING HOUSE AND PROPOSED ADDITION NEED TO COMPLY |
| | WITH ALL THE REQUIREMENTS OF FLOOD RESISTANT |
| | CONSTRUCTION, INCLUDING A FREEBOARD OF 2 FEET AS |
| | REQUIRED BY THE CITY ORDINANCE NO 4729-17 SEC. 18-290. |
| | PROVIDE COMPLETE PLANS AND CONSTRUCTION DOCUMENTS |
| | SHOWING COMPLIANCE WITH ALL THE FLOOD RESISTANT |
| | CONSTRUCTION. SPECIFY ON PLANS ALL FINISHED FLOOR |
| | ELEVATIONS BASED ON THE FLOOD MAPS THAT WENT INTO |
| | EFFECT ON OCTOBER 05, 2017. NOTE: REFERENCE THE |
| | ELEVATION DATUM USED ON THE NEW ADOPTED MAPS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED |
| | DURING CONSTRUCTION. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- ROOF TRUSS DESIGN CRITERIA SPECIFIED ON SHEET S.04 |
| | DOESN'T MATCH ROOF LOADS SPECIFIED THE BOTTOM LEFT OF |
| | SHEET S.01. REVISE AS REQUIRED TO MATCH. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | COLUMNS SUPPORTING THE SECOND FLOOR STUDY. FOUNDATION |
| | PLAN ON SHEET S.02 ONLY PROVIDE INFORMATION FOR THE |
| | FOOTING BUT NO INFORMATION FOR THE COLUMNS. ON THE |
| | OTHER HAND, THE WALL TYPE LEGEND AND PROPOSED FIRST |
| | FLOOR PLAN ON SHEET A.04 SHOWS WALL TYPE 3 TO BE A |
| | METAL FRAMED WALL. PROVIDE SPECIFICATIONS ABOUT |
| | REINFORCING WALL TO RECEIVE BEAM ABOVE. ALSO, SPECIFY |
| | CONNECTION OF BEAM TO BEARING WALL. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 6- PROVIDE COMPLETE MANUFACTURER'S DETAILS AND |
| | SPECIFICATIONS FOR THE PROPOSED FACTORY BUILT FIREPLACE |
| | AND CLAY FLUE SHOWING COMPLIANCE WITH SEC. R1004 |
| | FBC-RESIDENTIAL. |
| | NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN |
| | WRITING PRIOR TO SUBMITTAL. |
| | |
| | 7- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | THE TOP CONNECTIONS AT ALL STEEL COLUMNS SHOWN ON PLANS |
| | (INCLUDING THE ONES FOR THE MASTER BEDROOM BAY WINDOW). |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL |
| | THE STEEL COLUMNS SHOWN ON THE COLUMN & BASE PLATE |
| | SCHEDULE ON SHEET S.02. CLEARLY SHOW LOCATION OF ALL |
| | SPECIFIED ANCHOR BOLTS AND PROVIDE COMPLETE |
| | SPECIFICATIONS FOR THE WELDING OF THE STEEL COLUMN TO |
| | THE PLATE. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 8- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| | SCREWS. IF SPECIFYING ADHESIVE, THEN PRODUCT APPROVAL |
| | IS REQUIRED. |
| | |
| | 9- PROVIDE ICYNENE INSULATION ICC EVALUATION REPORT. |
| | MAKE SURE REPORT IS CURRENT. SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THEM IN |
| | WRITING PRIOR TO SUBMITTAL. |
| | |
| | 10- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR |
| | THE CARBON MONOXIDE ALARMS REQUIRED FOR ALL EXISTING |
| | BEDROOM AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL. |
| | |
| | 11- NOTE #1 BELOW WALL TYPE LEGEND ON SHEET A.04 |
| | SPECIFIES ROOF INSULATION TO BE ICYNENE. CLARIFY WHAT'S |
| | R3.6/INCH=R30 STANDS FOR? IS THIS 3.6 INCHES EQUIVALENT |
| | TO R-30 INSULATION?. NOTE: R-30 ICYNENE INSULATION |
| | REQUIRES MORE THAN 3.6 THICKNESS. SEE ICYNENE |
| | EVALUATION REPORT AND REVISE AS REQUIRED. SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 12- ROOF PLAN ON SHEET A.05: SPECIFY THE ROOF SLOPE OF |
| | THE FLAT ROOF AS REQUIRED BY SEC. R905.11.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 13- WINDOW SCHEDULE ON SHEET A.11 IS INCOMPLETE. IT |
| | DOESN'T SPECIFY TYPE OF WINDOWS AND NOT ALL THE WINDOWS |
| | SHOWN ON THE FLOOR PLAN ARE SPECIFIED ON THE WINDOW |
| | SCHEDULE. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 14- STAIR PLAN ON SHEET A.12: SPECIFY ALL DIMENSIONS. |
| | SEC. R311.7 FBC-RESIDENTIAL. |
| | |
| | 15- ORIENTATION OF EXTERIOR ELEVATIONS SPECIFIED ON |
| | DRAWINGS A.06, A.07, A.08 AND A.09 SEEMS TO BE |
| | INCORRECT. ACCORDING TO SURVEY AND AERIAL VIEW FROM THE |
| | PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE THE |
| | EXTERIOR ELEVATIONS ARE FACING MORE LIKE NORTHEAST, |
| | SOUTHEAST, SOUTHWEST AND NORTHWEST. REVISE AS REQUIRED. |
| | SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | NOTE: THIS IS AFFECTING HOW THE ENERGY CALCULATIONS |
| | WERE CALCULATED. ENERGY CALCULATIONS NEED TO BE REVISED |
| | AS WELL. |
| | |
| | 16- ENERGY CALCULATIONS SUBMITTED; |
| | A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE |
| | BOTTOM OF THE FORM SUBMITTED AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) WALL INSULATION R VALUE SPECIFIED ON ITEM #9 DOESN'T |
| | MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER THE WALL |
| | TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED TO MATCH. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) CEILING INFORMATION R VALUE SPECIFIED ON ITEM #10 |
| | DOESN'T MATCH R VALUE SPECIFIED BY THE ARCHITECT UNDER |
| | THE WALL TYPE LEGEND ON SHEET A.04. REVISE AS REQUIRED |
| | TO MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D) CLARIFY WHY THE CEILING R-VALUE IN PAGE 2 OF 4 IS |
| | 0.1?. IT DOESN'T MATCH INFORMATION SHOWN ON ITEM #10 ON |
| | PAGE 1 OF 4. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) ORIENTATION OF BUILDING DOESN'T MATCH THE ACTUAL |
| | ORIENTATION OF THE BUILDING. SEE SURVEY AND AERIAL VIEW |
| | FROM THE PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE |
| | AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. COORDINATE WITH ITEM #15 ABOVE. |
| | (EQUIPMENT SIZING CALCULATIONS SHOW THE CORRECT |
| | BUILDING ORIENTATION: FRONT DOOR FACES SOUTHEAST). |
| | |
| | F) WINDOWS INFORMATION SPECIFIED ON PAGE 3 OF 4 DOESN'T |
| | MATCH PLANS. REVISE AS REQUIRED. COORDINATE WITH ITEM |
| | #16(E) ABOVE. ALSO, REVISE THE WINDOWS AREA, AND |
| | OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC. |
| | R405.4.2 FBC-ENERGY CONSERVATION. |
| | |
| | 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) INSWING ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS. |
| | NOTE: PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| | CORRESPONDS TO DRAWINGS NO 1779 SUBMITTED. IF THERE IS |
| | NOT FLORIDA PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| | SUBMIT COMPLETE ORIGINAL ENGINEERING PACKAGE FOR |
| | BUILDING OFFICIAL APPROVAL. PLEASE CONTACT ME FOR MORE |
| | INFORMATION REGARDING SUBMITTAL PACKAGE FOR BUILDING |
| | OFFICIAL APPROVAL. |
| | |
| | B) FRENCH DOORS: ONLY ONE COPY OF NOA 14-1015.04 FOR |
| | SERIES "160 SENTINEL" ALUMINUM DOORS WAS SUBMITTED. |
| | PROVIDE 2 COPIES. |
| | |
| | C) SINGLE HUNG WINDOWS. ONLY ONE COPY OF NOA 15-0512.10 |
| | FOR SERIES "SENTINEL 110" ALUMINUM SINGLE HUNG WINDOW |
| | WAS SUBMITTED. PROVIDE 2 COPIES. |
| | |
| | D) FIXED WINDOWS. ONLY ONE COPY OF NOA 15-0413.03 FOR |
| | SERIES "SENTINEL 130" ALUMINUM FIXED WINDOW WAS |
| | SUBMITTED. PROVIDE 2 COPIES. |
| | |
| | E) WINDOW MULLIONS. ONLY ONE COPY OF NOA 14-1103.09 WAS |
| | SUBMITTED. PROVIDE 2 COPIES. |
| | |
| | F) ROOF TILE AS SPECIFIED ON PLANS. |
| | |
| | G) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF |
| | RECORD. NOTE: SEE ROOF TILE PRODUCT APPROVAL FOR LISTED |
| | ADHESIVES. |
| | |
| | H) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY MARK |
| | SPECIFIC ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE |
| | WITH THE CALCULATED DESIGN PRESSURES. NOTE: IF SELECTED |
| | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF |
| | ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS MAY |
| | BE NEED IT. |
| | |
| | I) HARDIE BOARD SOFFIT AS SHOWN ON DETAIL 7/A.05. |
| | |
| | J) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 18- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. NOTE: PLEASE PROVIDE REVIEW STAMP ON THE |
| | FRONT OF THE COVER (OR ANY OTHER FRONT PAGE) OF THE |
| | PRODUCT APPROVAL NOT ON THE BACK OF THE PAGE. THIS IS |
| | REQUIRED FOR PROPER SCANNING OF DOCUMENTS FOR RECORDS |
| | RETENTION. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |