| Plan Review Notes For Permit 17110512 |
| Permit Number |
17110512 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-18 17:39:17 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110512 | | | 10/18/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #4 FROM THE1ST REVIEW PRINTED BELOW STILL | | | EXISTS. A) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED IN | | | RESPONSE WITH A COPIED, AND REDUCED SIZE ENGINEER'S INK | | | SIGNATURE AND SEAL. PLEASE NOTE THAT ALL ENGINEERING | | | DOCUMENTS FILED FOR PUBLIC RECORD SHALL BEAR THE | | | ORIGNINAL SIGNATURE AND SEAL OF THE ENGINEER- SECTION | | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | B) PLEASE CLARIFY HOW SUBMITTAL OF THESE AC LOAD | | | CACLULATIONS ARE PROVING THE CLAIM THAT THE TEMPERATURE | | | DIFFERENTIAL BETWEEN THE HOOD MAKEUP AIR AND THE AIR IN | | | THE KITCHEN DOES NOT EXCEED 10 DEGREES FAHRENTHEIT. | | | THERE IS NO SPECIFIC MAKEUP AIR LOAD REFERENCED IN THE | | | CALCULATION AND THE EQUIPMENT SCHEDULE FOR THE SYSTEM | | | CONDITIONING THE KITCHEN HAS NOT BEEN PROVIDED. | | | | | | 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE | | | EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED | | | SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|