2018-10-18 17:39:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17110512
 10/18/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #4 FROM THE1ST REVIEW PRINTED BELOW STILL
 EXISTS. A) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED IN
 RESPONSE WITH A COPIED, AND REDUCED SIZE ENGINEER'S INK
 SIGNATURE AND SEAL. PLEASE NOTE THAT ALL ENGINEERING
 DOCUMENTS FILED FOR PUBLIC RECORD SHALL BEAR THE
 ORIGNINAL SIGNATURE AND SEAL OF THE ENGINEER- SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
 B) PLEASE CLARIFY HOW SUBMITTAL OF THESE AC LOAD
 CACLULATIONS ARE PROVING THE CLAIM THAT THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE HOOD MAKEUP AIR AND THE AIR IN
 THE KITCHEN DOES NOT EXCEED 10 DEGREES FAHRENTHEIT.
 THERE IS NO SPECIFIC MAKEUP AIR LOAD REFERENCED IN THE
 CALCULATION AND THE EQUIPMENT SCHEDULE FOR THE SYSTEM
 CONDITIONING THE KITCHEN HAS NOT BEEN PROVIDED.
  
 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1
  