Plan Review Notes
Plan Review Notes For Permit 17110512
Permit Number 17110512
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-22 08:57:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110512
 11/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUIFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE THERMAL CERAMICS
 GREASE DUCT WRAP.
  
 2) PROVIDE THE WIND DESIGN CRITERIA FOR INSTALLATION OF
 THE ROOF TOP FANS IN ACCORDANCE WITH SECTION 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 3) SUBMIT THE MIAMI-DADE NOA'S FOR THE ROOFTOP FANS.
  
 4) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  