| Plan Review Notes For Permit 17110499 |
| Permit Number |
17110499 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-14 13:49:10 | 1) ALL BACKFLOW DEVICES MUST BE LEAD FREE. THE | | | SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THIS DEVICE | | | IS LEAD FREE. CITY OF WPB MANUAL FOR CROSS CONNECTION | | | CONTROL. | | | 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF | | | SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. | | | THE SUBMITTED SPECIFICATIONS DO NOT SHOW THAT THIS | | | DEVICE IS LISTED ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL | | | LIST OF APPROVED DEVICES. | | | 3) IDENTIFY THE SIZE OF THE DEVICE ON THE PERMIT | | | APPLICATION AND ON THE SPECIFICATIONS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|