| Plan Review Notes For Permit 17110495 |
| Permit Number |
17110495 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-12-05 15:59:42 | 2 ND REVIEW RESPONSE: | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | DUE TO THIS PLAN BEING FAILED BY OTHER CITY DEPARTMENT | | | AND TO ENSURE PREVIOUS FIRE COMMENTS ARE ADDRESSED, THE | | | PREVIOUS PROVISO COMMENTS SHALL BE ADDRESSED ON ALL | | | FUTURE SUBMITTALS. | | | | | | | | | | | | 1) PLEASE PROVIDE ALL THE APPLICABLE DOCUMENTS OF THE | | | HOOD SUPPRESSION SYSTEM TESTING. A TEST OF THE SYSTEM | | | MAY BE REQUIRED BASED ON THE INSPECTION FINDINGS. | | | | | | PROVIDE APPLICABLE DOCUMENTS OF TESTING AND COMPLIANCE. | | | | | | | | | | | | 2) THE INSTALLATION OF THE LP TANKS SHALL BE UNDER | | | SEPARATE SHOP DRAWINGS. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) PLEASE ENSURE THERE IS A TYPE K AND ABC FIRE | | | EXTINGUISHER INSTALLED IN A APPLICABLE LOCATION. | | | | | | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS TO THE ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|