Plan Review Notes
Plan Review Notes For Permit 17110495
Permit Number 17110495
Review Stop E
Sequence Number 2
Notes
Date Text
2017-12-06 10:42:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A CONFLICT EXIST BETWEEN THE RISER DIAGRAM AND THE
 PANEL SCHEDULE FOR PANEL A. RISER SHOWS 3 - #3 COPPER
 GOING TO EACH STORAGE TRAILER, WHILE THE PANEL SCHEDULE
 SHOWS # 6 ON A 60 AMP BREAKER. ADDITIONALLY, THIS FEED
 IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR.
 PROVIDE CORRECTIONS. NEC 250.122; FBC 107.2.1
 2. PROVIDE PANELS SCHEDULES AND LOADS FOR THE STORAGE
 CONTAINER PANELS TO CONFIRM MAIN PANEL WILL NOT BE
 OVERLOADED. NEC 408.4, 408.30; FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  