| 2017-12-06 10:42:18 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. A CONFLICT EXIST BETWEEN THE RISER DIAGRAM AND THE | | | PANEL SCHEDULE FOR PANEL A. RISER SHOWS 3 - #3 COPPER | | | GOING TO EACH STORAGE TRAILER, WHILE THE PANEL SCHEDULE | | | SHOWS # 6 ON A 60 AMP BREAKER. ADDITIONALLY, THIS FEED | | | IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR. | | | PROVIDE CORRECTIONS. NEC 250.122; FBC 107.2.1 | | | 2. PROVIDE PANELS SCHEDULES AND LOADS FOR THE STORAGE | | | CONTAINER PANELS TO CONFIRM MAIN PANEL WILL NOT BE | | | OVERLOADED. NEC 408.4, 408.30; FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|