| 2017-12-07 07:13:44 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17110495 |
| | ADD: 2302 PRESIDENTIAL WAY |
| | CONT: MEP CONSTRUCTION GROUP |
| | TEL: 561-557-5840 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: THURS. DEC. 06/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE STEWARTS MOBILE |
| | KITCHEN CONCEPT IS TEMPORARY. THE 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION 108.1 |
| | STATES TEMPORARY STRUCTURES AND TEMPORARY USE PERMITS |
| | ARE LIMITED AS TO THE TIME OF SERVICE, BUT SHALL NOT BE |
| | PERMITTED FOR MORE THAN 6 MONTHS. |
| | IT IS THE CITYS UNDERSTANDING THIS UNIT MAY BE THERE UP |
| | TO A MINIMUM OF 2 YEARS MAKING THE INSTALLATION A |
| | PERMANENT STRUCTURE. |
| | |
| | 1A)2ND REQUEST. PLEASE REVIEW THE M-E-P & GAS COMMENTS. |
| | PLEASE PROVIDE WHAT AGENCY HAS LISTED OR CERTIFIED THE |
| | INSTALLATION OF THE ELECTRICAL, PLUMBING AND MECHANICAL |
| | EQUIPMENT WITHIN THE UNIT ITSELF. WITH THIS |
| | DOCUMENTATION THE CITYS RESPONSIBILITY WILL BE THE |
| | ATTACHMENT OF THE ELECTRICAL FROM THE UNIT AS WELL AS |
| | THE PLUMBING FROM THE UNIT ITSELF. |
| | 110.1.1 MANUFACTURERS AND FABRICATORS. WHEN DEEMED |
| | NECESSARY BY THE BUILDING OFFICIAL, HE/SHE SHALL MAKE, |
| | OR CAUSE TO BE MADE, AN INSPECTION OF MATERIALS OR |
| | ASSEMBLIES AT THE POINT OF MANUFACTURE OR FABRICATION. |
| | A RECORD SHALL BE MADE OF EVERY SUCH EXAMINATION AND |
| | INSPECTION AND OF ALL VIOLATIONS OF THE TECHNICAL |
| | CODES. |
| | |
| | 1B) 2ND REQUEST, NOT ADDRESSED. THE STEWARTS MOBILE |
| | KITCHEN WILL NEED TO BE TIED DOWN, ANCHORED TO THE |
| | GROUND TO RESIST THE MOMENT OF OVERTURNING, SLIDING |
| | ETC.? STEWARTS BROCHURE FOR THE MODEL K-100 -40 X8 |
| | MOBILE KITCHEN PAGE 2 UNDER THE HEADING CLIENTS |
| | RESPONSIBILITIES DOES INCLUDE THAT OF DEVELOPING A |
| | LEVEL AND COMPACTED GROUND SURFACE CAPABLE OF HOLDING A |
| | COMBINED TOTAL WEIGHT OF 60,000 LBS. PLEASE HAVE |
| | ENGINEERING FROM A FLORIDA P. E. FOR THE ANCHORING OF |
| | THIS UNIT SINCE IT IS NO LONGER TO BE CONSIDERED |
| | TEMPORARY. PROVIDE ANCHORING DETAILS FOR 170 MPH, 3 |
| | SECOND GUST, VULT. PLEASE ALSO PROVIDE AN ANALYSIS FOR |
| | THE RESISTING THE MOMENT OF OVERTURNING FROM THE EARTH |
| | ANCHORS SIZE AND DEPTH, STRAP SIZE AND SPACING AND PAD |
| | SIZE FOR THE UPRIGHT STATIONS. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | SOIL CONDITIONS/ANALYSIS |
| | WIND REQUIREMENTS |
| | FOUNDATION AND ANCHORING OF UNIT/ STRUCTURAL |
| | CALCULATIONS |
| | |
| | 2) THE SUBMITTED PLANS DOES NOT INDICATE IF THE FOOD IS |
| | SERVED DIRECTLY FROM THE UNIT OR IF THE FOOD IS |
| | PREPARED IN THE MOBILE UNIT AND TAKEN ELSEWHERE HERE |
| | ARE OUR CONCERNS: |
| | |
| | 2A) COMPLIED; CLIENTS DO NOT USE THE STRUCTURE TO GET |
| | THEIR FOOD, SERVERS. |
| | |
| | 2B) 2ND REQUEST. THE OTHER CONCERN IS UNDER THE CLIENTS |
| | RESPONSIBILITY IS TO PROVIDE DETAILS FOR AN ACCESSIBLE |
| | RAMPS, STAIRS, DECKS, GUARD RAILS AND HANDRAILS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | RAMP |
| | STAIRS |
| | DECKS |
| | HANDRAILS |
| | GUARDRAILS |
| | |
| | 201.3 TEMPORARY AND PERMANENT STRUCTURES. |
| | THESE REQUIREMENTS SHALL APPLY TO TEMPORARY AND |
| | PERMANENT BUILDINGS AND FACILITIES. |
| | |
| | ADVISORY 201.3. TEMPORARY AND PERMANENT STRUCTURES. |
| | TEMPORARY BUILDINGS OR FACILITIES COVERED BY THESE |
| | REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO, REVIEWING |
| | STANDS, TEMPORARY CLASSROOMS, BLEACHER AREAS, STAGES, |
| | PLATFORMS AND DAISES, FIXED FURNITURE SYSTEMS, WALL |
| | SYSTEMS, AND EXHIBIT AREAS, TEMPORARY BANKING |
| | FACILITIES, AND TEMPORARY HEALTH SCREENING FACILITIES. |
| | 201.4 SCOPE OF COVERAGE. THIS CODE APPLIES TO FIXED OR |
| | BUILT-IN ELEMENTS OF BUILDINGS, STRUCTURES, SITE |
| | IMPROVEMENTS AND PEDESTRIAN ROUTES OR VEHICULAR WAYS |
| | LOCATED ON A SITE. |
| | |
| | 2C) NEW COMMENT. THIS UNIT IS TO BE SET OVER 6 MONTHS |
| | WHICH MEANS IT IS NO LONGER CONSIDERED TEMPORARY, IT IS |
| | CONSIDERED PERMANENT, WAS NOT MANUFACTURED UNDER THE |
| | FLORIDA MANUFACTURED BUILDING PROGRAM AND HAS TO COMPLY |
| | WITH ALL OF THE CODE REQUIREMENTS OF THE 2014 FBC-B. |
| | 2014 FBC-B 1001.1BUILDINGS OR PORTIONS THEREOF SHALL BE |
| | PROVIDED WITH A MEANS OF EGRESS SYSTEM AS REQUIRED BY |
| | THIS CHAPTER. THE PROVISIONS OF THIS CHAPTER SHALL |
| | CONTROL THE DESIGN, CONSTRUCTION AND ARRANGEMENT OF |
| | MEANS OF EGRESS COMPONENTS REQUIRED TO PROVIDE AN |
| | APPROVED MEANS OF EGRESS FROM STRUCTURES AND PORTIONS |
| | THEREOF. |
| | FBC-B 1009 STAIRWAYS & LANDINGS |
| | 1010 RAMPS |
| | 1012 HANDRAILS |
| | 1013 GUARDS |
| | 1607 & TABLE 1607 LIVE LOADS DECKS AND STAIRS |
| | 1607.8.1 HANDRAILS AND GUARDS. |
| | 1607.8.1.1 CONCENTRATED LOAD. |
| | 1607.8.1.2 INTERMEDIATE RAILS. |
| | |
| | 2D) EXTERIOR COOLER. STEWARTS MOBILE CONCEPT LEASE |
| | QUOTE LIST (1) 8 X 12 FOOT MODULAR DUAL TEMP WALK IN |
| | UNIT, GROUND LEVEL ACCESS. THIS UNIT BEING A MODULAR |
| | BUILDING SHOULD HAVE BEEN BUILT UNDER THE STATE OF |
| | FLORIDA MODULAR BUILDING PROGRAM UNDER F. S. 553 PART |
| | I, 553.35-553.42. |
| | |
| | 3) COMPLIED. P. B. COUNTY FOR IMPACT FEE REVIEW. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |