| 2017-12-05 08:40:56 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17110495 |
| | 12/5/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I HAVE REVIEWED THE STATEMENT OF COMPLIANCE DOCUMENT |
| | FROM MEP CONSULTING ENGINEERS FOR THE MOBILE KITCHEN. |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS: |
| | |
| | A) THE LETTER DOES NOT INCLUDE THE FBC MECHANICAL CODE |
| | 5TH EDITION -2014 IN THE CODE COMPLIANCE STATEMENT. |
| | |
| | B) PLEASE CLARIFY THE FOLLOWING STATEMENT IN THE |
| | DOCUMENT- "STRUCTURE AND EQUIPMENT ARE IN ACCORDANCE TO |
| | MINIMUM STANDARDS FOR AUXILIARY KITCHEN USE". PLEASE |
| | INDICATE FROM WHICH CODE OR STANDARD THE "MINIMUM |
| | STANDARDS" ARE DERIVED FROM, AND PROVIDE AN ITEMIZED |
| | CHECKLIST OF ALL THE MECHANICAL EQUIPMENT AND SYSTEMS |
| | THAT WERE INSPECTED AND TESTED IN ACCORDANCE WITH THOSE |
| | |
| | STANDARDS. |
| | |
| | C) CLARIFY IF THE KITCHEN EXHAUST HOOD AND FIRE |
| | SUPPRESSION SYSTEMS WERE INSPECTED AS PART OF THE |
| | CERTIFICATION PROCEDURE. THE WEST PALM BEACH BUILDING |
| | DEPARTMENT POLICY REGARDING KITCHEN EXHAUST HOODS AND |
| | FIRE SUPPRESSION SYSTEMS IS THAT SEPARATE PERMITS ARE |
| | REQUIRED FOR EACH, AND COMPLETE ENGINEERED PLANS MUST |
| | BE SUBMITTED FOR REVIEW- PLEASE SEE SECTIONS 506, 507, |
| | 508, |
| | |
| | AND 509 FOR COMPLETE COMPLIANCE INFORMATION, AND SUBMIT |
| | PLANS AND SPECIFICATIONS UNDER SEPARATE PERMITS. |
| | |
| | D) PROVIDE A COMPLETE KITCHEN APPLIANCE AND EQUIPMENT |
| | LIST THAT INCLUDES THE MAKES AND MODELS OF THE COOKING |
| | APPLIANCES, THE KITCHEN HOOD, HOOD EXHAUST AND SUPPLY |
| | FANS. REFER TO THE CODE SECTIONS LISTED IN COMMENT 1C, |
| | AND ALSO SECTION 623 FBC-14 FUEL GAS. |
| | |
| | E) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR |
| | THE GAS-FIRED COOKING APPLIANCES AND PROVIDE A |
| | CALCULATION- SECTION 304 FBC-14 FUEL GAS. |
| | |
| | 2) THE SUBMITTED QUOTE FROM STEWART'S MOBILE CONCEPTS |
| | LTD. INCLUDES AN 8'X12' MODULAR DUAL TEMP WALK-IN UNIT. |
| | NO PLANS OR ENGINEERING CERTIFICATION HAS BEEN |
| | SUBMITTED FOR THE UNIT AND IT IS NOT SHOWN ON THE SITE |
| | PLAN. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL FOR |
| | THE UNIT MUST BE SUBMITTED AS REQUIRED BY FAC RULE |
| | 9N-3. |
| | |
| | 3) PLEASE ADJUST THE PERMIT VALUE ON THE APPLICATION TO |
| | MATCH THE DELIVERY, INSTALLATION, AND LEASE FEES LISTED |
| | IN THE QUOTE- SECTION 109.3 WPB AMENDMENTS TO THE FBC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |