Plan Review Notes
Plan Review Notes For Permit 17110469
Permit Number 17110469
Review Stop E
Sequence Number 1
Notes
Date Text
2017-11-28 07:30:44FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
 480 VOLT DISTRIBUTION IS ABOVE LICENSE ALLOWANCE, NEEDS
 ENGINEERS SEAL
  
 FBC-107.1 GENERAL - FAC 61G15-23.002 - PROVIDE A TITLE
 BLOCK FOR THE ENGINEER OF RECORD CONSISTENT WITH THE
 REQUIREMENTS OF THIS SECTION, E.G.: FIRM NAME, LICENSE
 NUMBER, PHONE NUMBER...ETC.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 VALUE SHOWN IS LOW, PLEASE PROVIDE A SIGNED CONTRACT
 FOR WORK PROVIDED.
  
  