| 2017-12-11 17:54:34 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17110463 | | | 12/11/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES. | | | | | | 3) PROVIDE KEY NOTES FOR THE SCOPE OF WORK RELATING TO | | | FIRE DAMPER INSTALLATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|