| Date |
Text |
| 2017-11-17 16:30:24 | |
| | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | 561-805-6718 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION |
| | |
| | 1. PLEASE PROVIDE THE USE OF ROOMS 116 AND 117. THE ONE |
| | DIMENSION IS LESS THAN 7 FEET. |
| | |
| | FBC 1208.1 MINIMUM ROOM WIDTHS. |
| | |
| | HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT |
| | LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION. |
| | KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN |
| | 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES |
| | OR COUNTER FRONTS AND WALLS. |
| | |
| | 2. IN SUITE 110 THE NEW TENANT SEPARATION WALL HAS LEFT |
| | THE TWO EXITS WITHIN 13 FT. OF EACH OTHER. THE DIAGONAL |
| | OF THE SPACE IS APPROXIMATELY 100 FEET. SEE EXCEPTION |
| | 2. |
| | FBC 1015.2 EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT. |
| | |
| | REQUIRED EXITS SHALL BE LOCATED IN A MANNER THAT MAKES |
| | THEIR AVAILABILITY OBVIOUS. EXITS SHALL BE UNOBSTRUCTED |
| | AT ALL TIMES. EXIT AND EXIT ACCESS DOORWAYS SHALL BE |
| | ARRANGED IN ACCORDANCE WITH SECTIONS FBC 1015.2.1 AND |
| | 1015.2.2. |
| | |
| | FBC 1015.2.1 TWO EXITS OR EXIT ACCESS DOORWAYS. |
| | WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED |
| | FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR |
| | EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART |
| | EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| | EXIT DOORS OR EXIT ACCESS DOORWAYS. INTERLOCKING OR |
| | SCISSOR STAIRS SHALL BE COUNTED AS ONE EXIT STAIRWAY. |
| | |
| | EXCEPTIONS: 2. WHERE A BUILDING IS EQUIPPED THROUGHOUT |
| | WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION FBC 903.3.1.1 OR 903.3.1.2, THE SEPARATION |
| | DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS |
| | SHALL NOT BE LESS THAN ONE-THIRD OF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |
| | |