Plan Review Notes
Plan Review Notes For Permit 17110439
Permit Number 17110439
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-21 12:49:231ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110439
 11/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BAG STORAGE BUILDING IS OMITTED FROM THE
 DESCRIPTION OF WORK ON THE PERMIT APPLICATION - PLEASE
 ADD THE BUILDING.
  
 2) THE JOB VALUE OF $800.00 ON THE APPLICATION APPEARS
 LOW FOR THE SCOPE OF WORK. IN ACCORDANCE WITH SECTION
 109.3 WPB AMENDMENTS TO THE FBC, PROVIDE A VALUE THAT
 INCLUDES LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN
 FEES, AND PROFIT
  
 AND OVERHEAD.
  
 3) NO MECHANICAL PLANS WERE SUBMITTED TO CLARIFY HOW
 THE BUIDINGS WILL BE VENTILATED. PLEASE PROVIDE PLANS
 THAT INCLUDE A SCOPE OF WORK OUTLINE, VENTILATION
 CALCULATIONS, AND INSTALLATION DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  