| Date |
Text |
| 2017-11-13 13:30:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO LOCATION INDICATED ON THE SITE PLAN |
| | WHERE THE PROPOSED TENT WILL BE LOCATED. PROVIDING A |
| | CLOUD AROUND A LARGE AREA WITH MULTIPLE BUILDINGS IS |
| | INSUFFICIENT. |
| | |
| | PLEASE PROVIDE THE EXACT LOCATION. |
| | |
| | |
| | 2) THE APPLICATION INDICATES THIS PROPOSED TENT FOR |
| | TEMPRARY PARKING FOR GALF CART PARKING. |
| | |
| | HOW LONG A TIME PERIOD IS BEING PROPOSED? |
| | |
| | PLEASE PROVIDE AN ENDING DATE. |
| | |
| | |
| | |
| | 3) THE APPLICATION INDICATES THIS PROPOSED TENT FOR |
| | TEMPRARY PARKING FOR GALF CART PARKING. |
| | |
| | ARE THESE ELECTRIC CARTS OR GASOLINE? |
| | |
| | IS THERE ANY ELECTRICITY BEING PROPOSED? USE OF |
| | EXTENSION CORDS? GASOLINE STORAGE CANS? |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATIONS OF ANY TIE-DOWN INFORMATION |
| | OR DIAGRAMS. |
| | |
| | HOW WILL THIS PROPOSED TENT BE SECURED? |
| | |
| | |
| | |
| | 5) THERE IS A PICTURE OF A SIDE-WALL TENT INFORMATION |
| | PATCH. WILL THIS PROPOSED TENT HAVE SIDEWALLS ALL |
| | AROUND? |
| | |
| | IF SO, WHERE WILL THE EXIT DOORS BE LOCATED? A MINIMUM |
| | OF TWO IS REQUIRED AND THEY SHALL BE SEPARATED PER NFPA |
| | 101, CHAPTER 7 MEANS OF EGRESS. |
| | |
| | |
| | |
| | 6) PER # 5 ABOVE, HOW WILL THE EXITS BE IDENTIFIED? |
| | |
| | PLEASE PROVIDE REQUIRED EXIT IDENTIFICATION. |
| | |
| | |
| | |
| | 7) THERE ARE NO FIRE EXTINGUISHERS INDICATED. |
| | |
| | PLEASE PROVIDE A MINIMUM OF ONE 10 ABC FE, HOWEVER, |
| | BASED ON # # 3 ABOVE 2 OR MORE MAY BE REQUIRED. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |