| Plan Review Notes For Permit 17110427 |
| Permit Number |
17110427 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-04 11:41:43 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110427 | | | 12/4/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE AC PLAN INDICATES A TOTAL OF 1420 | | | CFMS OF CONDITIONED AIR TO BE SUPPLIED BY THE 3.0-TON | | | SYSTEM. PROVIDE PRODUCT DATA FROM THE AC MANUFACTURER | | | TO CONFIRM THE SYSTEM CAN SUPPLY THAT MUCH AIR. | | | | | | 2) M-1: PROVIDE A PRODUCT DATA SHEET FOR THE 3" FLEX | | | DUCT. TYPICALLY, THE SMALLEST FLEX DUCT AVAILABLE IS A | | | 4" | | | | | | 3) THE OWNER/AGENT SHALL SIGN THE ENERGY COMPLIANCE | | | FORM R405-2014. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|