| 2017-11-14 08:45:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC-R310.1 REQUIRES EVERY SLEEPING ROOM TO HAVE AT | | | LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. | | | IN ORDER TO VERIFY THIS REQUIREMENT, PROVIDE A FLOOR | | | PLAN WITH THE ROOMS LABELED. SPECIFY THE TYPE AND SIZE | | | OF THE EXISTING WINDOWS ON THE PLANS. IF WINDOWS ARE | | | CONNECTED TO EACH OTHER USING MULLIONS SPECIFY THE SIZE | | | AND NUMBER OF THE WIDOWS IN THE OPENING. FBC 107.2.1 | | | | | | 2) A PRODUCT APPROVAL FOR STRUCTURAL MULLIONS WAS | | | SUBMITTED. INDICATE THE CONFIGURATION OF THE WIDOWS | | | WEAR THIS WILL BE INSTALLED. IN ORDER TO REVIEW THE | | | MULLIONS FOR CODE COMPLIANCE THE MULLION SPAN AND | | | TRIBUTARY WIDTH ARE REQUIRED.FBC - R301.2.1 | | | | | | 3) THE PRODUCT CERTIFICATION AND INSTALLATION | | | INSTRUCTIONS THAT ARE ATTACHED TO THE HORIZONTAL | | | SLIDING WINDOW FL16804 ARE NOT THE ONES FOR THE XO, OX | | | CONFIGURATIONS THAT WERE CIRCLED BY YOU ON PAGE 2 OF | | | THE PRODUCT APPROVAL. PLEASE CORRECT. FBC 107.2.1 | | | | | | |
|