| Plan Review Notes For Permit 17110392 |
| Permit Number |
17110392 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-27 15:49:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. ALL ITEMS OTHER THAN BUILDING, ROOFING, MECHANICAL, | | | ELECTRICAL, PLUMBING REQUIRE SEPARATE PERMITS AND | | | SEPARATE FEES, FBC 107. PLEASE SUBMIT A PERMIT | | | APPLICATION AND THE SAME NUMBER WILL BE USED FOR THE | | | PERMIT. | | | | | | 2. THE FLAGPOLE IS CONSIDERED A STRUCTURE WHICH IS | | | REQUIRED TO RESIST WIND LOADS. PROVIDE AN ENGINEERED | | | DETAIL, INCLUDING WIND DESIGN CRITERIA, FLORIDA STATUTE | | | 471. THE SOILS REPORT FOR THIS PARCEL SHOULD BE | | | REVIEWED BY DESIGNER OF FLAGPOLE PRIOR TO DESIGN; | | | INDICATE REVIEW ON ENGINEERING (OR IN A SEPARATE REVIEW | | | LETTER). | | | | | | 3. SEE THE SHOP DRAWING FOR THE FLAGPOLE, FOUNDATION IS | | | EXCLUDED FROM THE DESIGN. PLEASE INCLUDE FOUNDATION | | | DESIGN IN THE FLAGPOLE ENGINEERING. | | | | | | 4. THERE ARE A NUMBER OF REDLINES ON THE SHOP DRAWINGS. | | | INCORPORATE INTO THE ENGINEERING, FS 471. FOR INSTANCE, | | | FLAGPOLE WAS DESIGNED FOR A SPECIFIED SIZE OF FLAG; | | | THIS AFFECTS RESISTANCE TO WIND LOADS AND THEREFORE | | | CANNOT BE DONE WITH REDLINES BUT SHOULD BE INCORPORATED | | | INTO THE ENGINEERING. | | | | | | |
|