| Plan Review Notes For Permit 17110388 |
| Permit Number |
17110388 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-13 16:05:47 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110388 | | | 8/13/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) BASED ON THE SUBMITTED AC SIZING CALCULATIONS FOR | | | THE KITCHEN, ALEX KHAROSKA OF CREDO CONSULTING | | | ENGINEERS IS STATING IN HIS LETTER THAT THE EXISTING | | | 8-TON COOLING SYSTEM PERMITTED UNDER THE MASTER PERMIT | | | #17020359, MUST BE ENLARGED TO A 10-TON SYSTEM TO | | | ABSORB THE ADDITIONAL HEAT LOAD IN THE KITCHEN FROM THE | | | EXHAUST HOOD MAKE UP AIR. PLEASE PROVIDE A PERMIT | | | APPLICATION AND PLAN FOR ENLARGING THE SYSTEM.- SECTION | | | 107.2.1 WEST PALM BEACH AMENDMENTS TO THE FBC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|