Plan Review Notes
Plan Review Notes For Permit 17110388
Permit Number 17110388
Review Stop M
Sequence Number 2
Notes
Date Text
2018-02-28 17:04:292ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17110388
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN AN EFFORT TO SHOW THE COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE FOR THE KITCHEN HOOD
 EXHAUST SYSTEM, THE ENGINEER HAS SUBMITTED AC LOAD
 CALCULATIONS , HOWEVER THE CALCULATIONS PROVIDE GENERAL
 HEAT LOAD DATA FOR THE KITCHEN IN BTUH, BUT DO NOT
 SPECIFICALLY INDICATE THE HEAT LOAD FROM THE MAKEUP
 AIR, OR INDICATE THAT THE AC SYSTEM HAS BEEN SIZED TO
  
 ACCOMODATE THE ADDED LOAD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  