Plan Review Notes
Plan Review Notes For Permit 17110388
Permit Number 17110388
Review Stop M
Sequence Number 1
Notes
Date Text
2017-11-18 08:55:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17110388
 11/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) VERIFY COMPLIANCE WITH SECTION 508.1.1: MAKEUP AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ROOFTOP FANS AND THE MAKEUP AIR DUCT ON THE
 EXTERIOR WALL. PLEASE PROVIDE THE DESIGN CRITERIA PER
 SECTION 1609 FBC-014 BUILDING, AND THE MIAMI-DADE NOA'S
 FOR THE FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  