| Plan Review Notes For Permit 17110388 |
| Permit Number |
17110388 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-18 08:55:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17110388 | | | 11/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) VERIFY COMPLIANCE WITH SECTION 508.1.1: MAKEUP AIR | | | TEMPERATURE. | | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | | HVAC SYSTEM. | | | | | | 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE ROOFTOP FANS AND THE MAKEUP AIR DUCT ON THE | | | EXTERIOR WALL. PLEASE PROVIDE THE DESIGN CRITERIA PER | | | SECTION 1609 FBC-014 BUILDING, AND THE MIAMI-DADE NOA'S | | | FOR THE FANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|