| 2017-11-27 15:01:05 | 11-27-2017 1ST GAS REVIEW**DENIED** |
| | |
| | 1) YOUR GAS RISER / ISOMETRIC CONFLICTS WITH CITY |
| | RECORDS. YOUR TOTAL P.E IS LISTED AS 40" BUT CITY |
| | RECORDS SHOWS 125' . ALSO CITY RECORDS SHOW THE FURTURE |
| | GENERATOR SIZE AS 500,000BTU BUT YOUR PROPOSING A |
| | 750,000 BTU GENERATOR. PROVIDE A COMPLETE RISER/ |
| | ISOMETRIC ON THE COMPLETE GAS SYSTEM.FGC SECS. 401.4, |
| | 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, |
| | G2412.8, G2413.1, G2413.2, G2413.3 |
| | |
| | 2) PROVIDE CORRECT FUEL TABLE OF SCH 40 METALLIC PIPING |
| | FOR .5LB. SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 |
| | FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. |
| | G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1 |
| | |