Plan Review Notes For Permit 17110370
Permit Number 17110370
Review Stop G
Sequence Number 1
Notes
Date Text
2018-01-19 07:41:5601/19/2018 GAS 2ND REVIEW**FAILED**
  
 1) YOU ARE STILL MISSING THE SIZING TABLE FIR .5LB SCH
 40 METAL PIPING. 2ND REQEST.SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2014 FBC-FUEL GAS SECS. 401.4, 401.8 THRU
 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014
 FBC-RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 2) YOUR GAS PRESSURE REGULATORS ARE NOT DESIGNED FOR
 DOWNSTREAM USAGE AND ALSO MUST COMPLY WITH FUEL AND GAS
 CODE. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 3) SHOW THE DISTANCE OF PIPING FROM THE 2 PSI REGULATOR
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION