| Plan Review Notes For Permit 17110370 |
| Permit Number |
17110370 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-19 07:41:56 | 01/19/2018 GAS 2ND REVIEW**FAILED** | | | | | | 1) YOU ARE STILL MISSING THE SIZING TABLE FIR .5LB SCH | | | 40 METAL PIPING. 2ND REQEST.SUBMIT TWO COPIES OF THE | | | APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR | | | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH | | | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD | | | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER | | | TO THE 2014 FBC-FUEL GAS SECS. 401.4, 401.8 THRU | | | 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014 | | | FBC-RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & | | | G2413.3. | | | | | | 2) YOUR GAS PRESSURE REGULATORS ARE NOT DESIGNED FOR | | | DOWNSTREAM USAGE AND ALSO MUST COMPLY WITH FUEL AND GAS | | | CODE. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2014 FGC SEC.410.1. | | | | | | 3) SHOW THE DISTANCE OF PIPING FROM THE 2 PSI REGULATOR | | | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE | | | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|