| 2017-12-07 05:14:27 | 1.) NOTE ON THE PLANS THE TYPE AND SIZE OF THE PIPE ON |
| | THE OUTLET OF THE GAS METER. PIPE SHALL BE SIZED FOR |
| | THE TOTAL BTU LOAD OF THE SYSTEM INCLUDING FUTURE |
| | APPLIANCES. FBC-FUEL GAS SEC.402.2. |
| | 2) SHOW THE SIZE AND TYPE OF PIPE DOWNSTREAM OF EACH |
| | PRESSURE REGULATOR AT EACH APPLIANCE. |
| | 3) SHOW THE DISTANCE FROM EACH PRESSURE REGULATOR TO |
| | THE APPLIANCE. IF ALL ARE LESS THAN 10 FEET INDICATE SO |
| | ON THE PLANS. |
| | 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3.YOU HAVE SUBMITTED |
| | A COPY OF THE TABLE FOR THE PE BUT WHAT ABOUT THE LOW |
| | PRESSURE SYSTEM? THE TYPE OF PIPING BEING USED FOR THE |
| | LOW PRESSURE SYSTEM IS NOT EVEN NOTED ON THE PLANS SO A |
| | COMPLETE REVIEW COULD NOT BE DONE. 2ND REQUEST. |
| | 5) SIZE THE PE BRANCHES TO THE BBQ AND THE FUTURE |
| | STOVE. |
| | 6) REGULATORS INSTALLED OUTDOORS SHALL BE APPROVED FOR |
| | EXTERIOR USE. FBC-FUEL GAS SEC.410.1. MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS SHALL BE |
| | ONSITE FOR FINAL INSPECTION. FBC FUEL GAS SEC.410.1, |
| | 305.1. |
| | 7) FUTURE OUTLETS FOR APPLIANCES SHALL BE EQUIPEED WITH |
| | A LISTED SHUTOFF VALVE, A LINE PRESSURE REGULATOR AND A |
| | PLUG OR NIPPLE AND CAP. |
| | NOTE** THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES |
| | / EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| | FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |