| 2017-11-21 10:16:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROPOSED WORK IS NOT WITHIN THE SCOPE OF WORK |
| | PERMITTED FOR THE LICENSE TYPE OF CONTRACTOR. PROVIDE |
| | ELECTRICAL CONTRACTOR THAT HAS THE PROPER LICENSING FOR |
| | THIS TYPE OF WORK. FBC 105.1; FS 489.105(3), 489.505 |
| | 2. ADDRESS LISTED ON PLAN DOES NOT MATCH THE ADDRESS |
| | STATED ON PERMIT APPLICATION. PROVIDE CORRECT ADDRESS |
| | ON PLANS. FBC 107.2.1 |
| | 3. GENERAL NOTES ON SHEET PS-1 STATES THAT THE |
| | ELECTRICAL CODE FOR THIS PROJECT IS THE 2012 NATIONAL |
| | ELECTRICAL CODE, WHICH DOES NOT EXIST. PROVIDE CORRECT |
| | CODE REFERENCES. 2014 FBC PREFACE |
| | 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED |
| | TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC |
| | 107.2.1, FS 471, 481 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |