2017-11-21 10:16:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROPOSED WORK IS NOT WITHIN THE SCOPE OF WORK
 PERMITTED FOR THE LICENSE TYPE OF CONTRACTOR. PROVIDE
 ELECTRICAL CONTRACTOR THAT HAS THE PROPER LICENSING FOR
 THIS TYPE OF WORK. FBC 105.1; FS 489.105(3), 489.505
 2. ADDRESS LISTED ON PLAN DOES NOT MATCH THE ADDRESS
 STATED ON PERMIT APPLICATION. PROVIDE CORRECT ADDRESS
 ON PLANS. FBC 107.2.1
 3. GENERAL NOTES ON SHEET PS-1 STATES THAT THE
 ELECTRICAL CODE FOR THIS PROJECT IS THE 2012 NATIONAL
 ELECTRICAL CODE, WHICH DOES NOT EXIST. PROVIDE CORRECT
 CODE REFERENCES. 2014 FBC PREFACE
 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  