| 2018-02-07 15:10:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. NEW COMMENTS |
| | ARE ADDED BELOW PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (NOT |
| | PROVIDED.) |
| | 3. ALL KITCHEN RECEPTACLE OUTLETS ARE REQUIRED TO BE |
| | GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8 (ONE |
| | OUTLET STILL IS SHOWN WITH NO GFCI PROTECTION.) |
| | 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2, |
| | 405.2.2.2 (NOT PROVIDED.) |
| | 5. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE |
| | ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA |
| | 96. NFPA 96, SECTION 10.4.1, FBC 107.2.1 (NOT |
| | PROVIDED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 6. PROVIDE LOCATION OF PANEL FOR KITCHEN. FBC 107.2.1 |
| | 7. CONDUIT FROM EXTERIOR DISCONNECT TO INTERIOR PANEL |
| | IS REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR. |
| | PROVIDE CORRECTION. NEC 250.122 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |