Plan Review Notes
Plan Review Notes For Permit 17110339
Permit Number 17110339
Review Stop P
Sequence Number 1
Notes
Date Text
2017-11-28 16:11:481ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GREASE INTERCEPTOR SPECIFICATIONS AND SANITARY
 RISER ARE TO SMALL PLEASE ENLARGE ON PLAN SHEET. PER
 WPB AMEND TO FBC 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
 2. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR
 GREASE INTERCEPTOR. PER FBC PL 1003.2
  
 3. THE RISER DIAGRAM DOES NOT MATCH FLOOR PLAN THE HAND
 SINK IS NOT SHOWN ON FLOOR PLAN AND THE 3" VENT IS NOT
 SHOWN ON RISER. PER WPB AMEND TO FBC 107.2.1
  
 4. A TRAP PRIMER IS REQUIRED ON FLOOR DRAINS. PER FBC
 PL 1002.4
  
 5. PLEASE PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 6. SHOW LOCATION OF WATER HEATER ON PLAN SHALL COMPLY
 WITH FBC PL 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 7. A CLEANOUT IS REQUIRED ON INLET SIDE OF GREASE
 INTERCEPTOR AND A TESTPORT/ CLEAN OUT MIN 4" REQUIRED
 ON OUTLET SIDE. PER WPB UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  