| 2017-11-28 16:11:48 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE GREASE INTERCEPTOR SPECIFICATIONS AND SANITARY |
| | RISER ARE TO SMALL PLEASE ENLARGE ON PLAN SHEET. PER |
| | WPB AMEND TO FBC 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF |
| | FLORIDA STATUTES. |
| | |
| | 2. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FOR |
| | GREASE INTERCEPTOR. PER FBC PL 1003.2 |
| | |
| | 3. THE RISER DIAGRAM DOES NOT MATCH FLOOR PLAN THE HAND |
| | SINK IS NOT SHOWN ON FLOOR PLAN AND THE 3" VENT IS NOT |
| | SHOWN ON RISER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. A TRAP PRIMER IS REQUIRED ON FLOOR DRAINS. PER FBC |
| | PL 1002.4 |
| | |
| | 5. PLEASE PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO |
| | FBC 107.3.5.1.3(13) |
| | |
| | 6. SHOW LOCATION OF WATER HEATER ON PLAN SHALL COMPLY |
| | WITH FBC PL 607.2 HOT OR TEMPERED WATER SUPPLY TO |
| | FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | |
| | 7. A CLEANOUT IS REQUIRED ON INLET SIDE OF GREASE |
| | INTERCEPTOR AND A TESTPORT/ CLEAN OUT MIN 4" REQUIRED |
| | ON OUTLET SIDE. PER WPB UTILITIES DEPT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |