2017-11-14 12:51:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PLEASE ENSURE THAT THE LOCKS AND LATCHES ON BOTH
 EXIT DDORS COMPLY WITH NFPA 101, CHAPTER 7 MEANS OF
 EGRESS.
  
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3,
 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
 7.2.1.5.12* DEVICES SHALL NOT BE INSTALLED IN
 CONNECTION WITH ANY DOOR ASSEMBLY ON WHICH PANIC
 HARDWARE OR FIRE EXIT HARDWARE IS REQUIRED WHERE SUCH
 DEVICES PREVENT OR ARE INTENDED TO PREVENT THE FREE USE
 OF THE LEAF FOR PURPOSES OF EGRESS, UNLESS OTHERWISE
 PROVIDED IN 7.2.1.6.
  
 PETER LEDUC
 FIRE MARSHAL