Date Text
2017-11-18 08:11:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17110339
 ADD: 4600 N. FLAGLER DR.
 CONT: MICHAEL ENNIS CONSTRUCTION CO.
 TEL: 772-486-2373
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 18/ 2017
 ACTION: DENIED
  
 1) IT WOULD APPEAR THE CONTRACTOR NEEDS TO TAKE
 OWNERSHIP OF THE PLANS, SINCE THE CONSTRUCTION COMPANY
 NAME APPEARS IN THE TITLE BLOCK.
 CERTIFICATION BY CONTRACTOR. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR.
  
 2) SHEET # 1 THE COVERSHEET INDICATES THE CLOSING IN OF
 A WINDOW ON A WOOD FRAME STRUCTURE, THE PLANS INDICATE
 2 X 6 STUDS TO BE INSTALLED AT 16 INCHES ON CENTER BUT
 THE PLANS DOES NOT INDICATE HOW THE STUDS WILL BE
 ANCHORED (STRAPPED) TO THE FRAMING MEMBERS AROUND THE
 EXISTING WINDOW TO BECOME PART OF THE
 MAIN WIND FORCE RESISTING SYSTEM (MWFRS)? THE WIND
 SPEED AT THE JOBSITE LOCATION IS 170 VULT MPH, 3SECOND
 GUST & EXPOSURE D.
  
 2014 FBC-B 2308.2.1 ULTIMATE DESIGN WIND SPEED GREATER
 THAN 115 MPH (3-SECOND GUST).
 WHERE THE ULTIMATE DESIGN WIND SPEED, VULT EXCEEDS 115
 MPH (3-SECOND GUST), THE PROVISIONS OF EITHER AF&PA
 WFCM OR ICC 600 ARE PERMITTED TO BE USED. WIND SPEEDS
 IN FIGURES 1609A, 1609B, AND 1609C SHALL BE CONVERTED
 IN ACCORDANCE WITH SECTION 1609.3.1 FOR USE WITH ICC
 600.
  
 3) SHEET # 1 THE COVERSHEET INDICATES THE CLOSING IN OF
 A WINDOW ON A WOOD FRAME STRUCTURE, THE PLANS INDICATE
 WIRE LATH AND STUCCO TO BE INSTALLED WHERE THE INFILL
 OF THE WINDOW WILL OCCUR.
 PLEASE SHOW COMPLIANCE WITH 2 LAYERS OF WATER RESISTANT
 BARRIERS INSTALLED INDEPENDENTLY. SEE 2014 FBC-B 2510.6
 WATER-RESISTANT BARRRIERS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER