| Plan Review Notes For Permit 17110331 |
| Permit Number |
17110331 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-09 10:18:19 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT (2 STORY STRUCTURE) AND | | | THE ROOF SLOPE OF THE STRUCTURE. FBC 107.2.1, | | | FBC-R301.2.1 | | | | | | 2) FROM THE POLYGLASS PRODUCT APPROVAL ( FL5259-R25) | | | SPECIFY WHICH ONE OF THE POLYGLASS UNDERLAYMENTS WILL | | | BE USED AND ITS MAXIMUM DESIGN PRESSURE. FBC 107.2.1, | | | FBC-R905.3.3 | | | | | | |
|