| Plan Review Notes For Permit 17110329 |
| Permit Number |
17110329 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-09 12:11:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT (2 STORY STRUCTURE) AND | | | THE ROOF SLOPE OF THE STRUCTURE. FBC 107.2.1, | | | FBC-R301.2.1 | | | | | | 2) THIS TWO STORY STRUCTURE IS LOCATED IN EXPOSURE | | | CATEGORY D WITH A 170 MPH WIND SPEED. THE PRODUCT | | | APPROVAL THAT WAS SUBMITTED FOR THE METAL ROOFING HAS A | | | MAXIMUM UPLIFT DESIGN PRESSURE OF -71 PSF. THIS UPLIFT | | | IS NOT ADEQUATE FOR THE REQUIRED UPLIFT PRESSURES IN | | | THE PERIMETER AND CORNER ROOF AREAS. FBC-R301.2.1 |
|