| Plan Review Notes For Permit 17110321 |
| Permit Number |
17110321 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-17 16:25:06 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODE | | | PERMIT #17110321 | | | 11/17/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) M2.1: PROVIDE THE FLEX DUCT SIZES | | | | | | 3) M2.1: PLEASE CLARIFY IF THE VAV BOX BY ROOM 105 IS | | | NEW OR EXISTING. | | | | | | 4) INDICATE IF THERE ARE ANY COOKING APPLIANCES IN THE | | | NEW CAFE AND PROVIDE EXHAUST VENTILATION WHERE | | | REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|