| Plan Review Notes For Permit 17110319 |
| Permit Number |
17110319 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-11-29 07:41:21 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE | | | 405.2 | | | | | | EXTERIOR LIGHTING CONTROLS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED | | | BY EITHER A COMBINATION OF A PHOTOSENSOR AND A TIME | | | SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING | | | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | FBC CE 405.2.4 | | | | | | |
|