| 2017-11-14 06:20:01 | 1) THE GAS DRAWING SHOWS PS-II UNDERGROUND PIPING FOR |
| | THE OUTDOOR FIREPLACE AT A 12 INCH WATER COLUMN BUT |
| | THERE IS NO LINE PRESSURE REGULATOR ON THIS LINE |
| | REDUCING THE PRESSURE FROM 2 PSI TO 12 INCHES OF WATER |
| | COLUMN. CLARIFY. |
| | 2) THE GAS DRAWING NOTES THAT THE LONGEST EXTERIOR RUN |
| | IS 60 FEET BUT THE PLANS SHOW A TOTAL OF 140 FEET OF |
| | UNDERGROUND PIPING FROM THE GAS METER TO OUTDOOR |
| | FIREPLACE. THERE IS NO LINE PRESSURE REGULATOR SHOWN ON |
| | THE PLAN FOR THE FIREPLACE. CLARIFY. SEE COMMENT #1. |
| | 3) THE 1/2 INCH GALVANIZED LINE AT THE GAS REGULATOR |
| | SUPPLYING THE COOKTOP AND THE GRILL CAN ONLY SUPPLY |
| | 65,000 BTU'S AT 60 FEET PER TABLE 402.4 (2) OF THE FUEL |
| | GAS CODE. THIS LINE WILL NEED TO BE 3/4 INCH. |
| | 4) THE 10 FEET SECTION OF 3/4 INCH CSST WITH AN EHD OF |
| | 25 MUST BE A MINIMUM OF 1 INCH WITH AN EHD OF 30 PER |
| | TABLE 402.4 (15). THE TOTAL LENGTH OF 60 FEET IN TABLE |
| | 402.4 (15) SHALLL BE USED. |
| | 5) THE MINIMUM DISTANCE FOR THE SIZING OF THE SCH. 40 |
| | METALLIC PIPE FOR THE POOL HEATER FROM THE REGULATOR TO |
| | THE HEATER SHALL BE 10 FEET PER TABLE 402.4 (2). A 3/4 |
| | INCH LINE AT 10 FEET CAN ONLY SUPPLY 360,000 BTU'S. THE |
| | LOW PRESSURE LINE SHALL BE A MINIMUM OF 1 INCH PER THE |
| | TABLE. |
| | 6) SHOW THE PIPE SIZE OF THE RISERS FROM THE |
| | UNDERGROUND PIPING TO THE LINE PRESSURE REGULATORS. |
| | 7) THE PLANS REFERENCE TABLE 402.4 (21) OF THE FUEL GAS |
| | CODE WHICH IS FOR PE PIPE AT LESS THAN 2 PSI BUT THE |
| | GAS PLAN SHOWS ALL THE PE PIPE SERVING 2 PSI. CLARIFY. |
| | 8) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE GAS REGULATORS. WPB AMEND. TO |
| | FBC SEC. 107.1. |
| | 9) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | ON THE INSIDE OR OUTSIDE OF THE STRUCTURE.THE LOCATION |
| | OF THE TANKLESS WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION MANUAL. MOST MANUFACTURER'S |
| | REQUIRE OUTSIDE UNITS TO BE INSTALLED A MINIMUM OF FOUR |
| | FEET FROM AN OPERABLE DOOR OR WINDOW. |
| | 10) SUBMIT TWO COPIES OF A FLOOR PLAN SSHOWING THE |
| | LOCATION OF ALL GAS APPLIANCES. WPB AMEND. TO FBC SEC. |
| | 107.1. |
| | 11) SUBMIT TWO COPIES OF MANUFACTURER'S INSTALLATION |
| | SPECIFICATIONS FOR THE PS-II PIPING.WPB AMEND. TO FBC |
| | SEC. 107.1. |
| | 12) VENT LIMITING DEVICES ARE USUALLY APPROVED FOR |
| | INDOOR USE ONLY. VENT PROTECTORS ARE REQUIRED IF USED |
| | ON REGULATORS LOCATED OUTSIDE. |
| | |