| 2018-09-05 15:44:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE3901.7 (NOT |
| | PROVIDED) |
| | 3. PROVIDE FULL FLOOR PLAN SHOWING ALL SMOKE/CO ALARMS |
| | IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. ADDITIONALLY, NEW BEDROOMS |
| | DO NOT SHOW THE REQUIRED SMOKE ALARM. PROVIDE |
| | CORRECTION. SMOKE ALARMS MUST BE AT LEAST 3 FEET FROM |
| | CEILING FAN OR MECHANICAL REGISTER. NFPA 72; 29.8.3.6 |
| | AND 7; FBC R314.3, FBC 107.2.1 (NOT PROVIDED. |
| | ADDITIONALLY, A CARBON MONOXIDE ALARM IS REQUIRED |
| | WITHIN 10 FEET OF EACH SLEEPING ROOM, WHICH IS NOT |
| | CURRENTLY SHOWN.) |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. A NOTE ON MECHANICAL SHEET STATES THAT THE |
| | CONTRACTOR MAY INSTALL A MINI-SPLIT SYSTEM IN LIEU OF |
| | EXTENDING THE EXISTING A/C SYSTEM. IF THIS IS THE CASE, |
| | IT APPEARS THAT THE CURRENT ELECTRICAL SYSTEM WOULD BE |
| | OVERLOADED, BASED ON THE LOAD CALCULATION PROVIDED. |
| | PROVIDE CLARIFICATION WHICH METHOD WILL BE USED. FBC |
| | 107.2.1 (NOT PROVIDED) |
| | |
| | NEW COMMENT: |
| | |
| | 7. PLAN SHOWS AN EXTERIOR GFCI ON THE SIDE OF THE HOUSE |
| | ON CIRCUIT 19A, WHICH IS THE SAME CIRCUIT USED FOR |
| | BATHROOM. THIS IS SHOWN AS A 15 AMP CIRCUIT. A MINIMUM |
| | OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO |
| | SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS |
| | SHALL HAVE NO OTHER OUTLETS. PROVIDE CORRECTION. NEC |
| | 210.11(C)(3) , FBC RE E3703.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |