| Plan Review Notes For Permit 17110286 |
| Permit Number |
17110286 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-07 15:51:00 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2 | | | COPIES) BASED ON THE ORIENTATION OF THE BUILDING AS | | | REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH | | | EDITION (2014). | | | | | | 2- MECHANICAL PLAN M.1: | | | A) SPECIFY THE EQUIPMENT LISTED IN THE EQUIPMENT SIZING | | | CALCULATIONS. COORDINATE WITH ITEM #1 ABOVE. SEC. | | | 107.3.5.3 CITY AMENDMENTS. | | | | | | B) SPECIFY THE SIZE OF ALL DUCTWORK. SEC. 107.3.5.3 | | | CITY AMENDMENTS. | | | | | | C) REVISE THE A/C ANCHOR DETAIL: THERE ARE NO | | | SPECIFICATIONS FOR THE PLATE CONNECTING THE CONDENSER | | | UNIT TO THE CONCRETE SLAB. PROVIDE COMPLETE | | | SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|