Plan Review Notes
Plan Review Notes For Permit 17110283
Permit Number 17110283
Review Stop P
Sequence Number 4
Notes
Date Text
2019-01-22 11:47:44APPROVED
 PLUMBING PROVISO
 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL
 EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER
 CHECK VALVE PER FBC PL 607.3. SEE RED LINED COMMENTS ON
 DETAIL 5 OF PLAN PAGE P5.1 FOR CLARIFICATION.
  
  