2018-11-27 14:11:423RD REVIEW: DENIED
 PLUMBING COMMENTS
 REVIEWED PLAN SHEETS PO.1, P1.1, P1.2, P2.1, P3.1,
 P4.1, P5.1, P5.2 & P6.1
  
 AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING
 COMMENTS APPLY.
  
 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL
 EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER
 CHECK VALVE PER FBC PL 607.3.
 2. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1 SHOWS 140
 DEGREE HOT WATER TO FIXTURES. EWH SCHEDULE ON PLAN PAGE
 P6.1 CALLS FOR TEMPERATURE TO BE SET AT 110 DEGREES.
 PLEASE CLARIFY.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  