| Plan Review Notes For Permit 17110283 |
| Permit Number |
17110283 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-11-27 14:11:42 | 3RD REVIEW: DENIED | | | PLUMBING COMMENTS | | | REVIEWED PLAN SHEETS PO.1, P1.1, P1.2, P2.1, P3.1, | | | P4.1, P5.1, P5.2 & P6.1 | | | | | | AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING | | | COMMENTS APPLY. | | | | | | 1. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1. THERMAL | | | EXPANSION TANK SHALL BE PLACED DOWNSTREAM OF COLD WATER | | | CHECK VALVE PER FBC PL 607.3. | | | 2. RE: EWH-1; DETAIL 5 ON PLAN PAGE P5.1 SHOWS 140 | | | DEGREE HOT WATER TO FIXTURES. EWH SCHEDULE ON PLAN PAGE | | | P6.1 CALLS FOR TEMPERATURE TO BE SET AT 110 DEGREES. | | | PLEASE CLARIFY. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|