| 2018-11-08 11:19:36 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODE | | | PERMIT #17110283 | | | 11/8/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | | 1 - PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL | | | GAS. | | | | | | 2 - PROVIDE CUT SHEETS FOR COOKING APPLIANCES | | | | | | 3 - BE ADVISED 2014 FLORIDA MECHANICAL CODE 508.1.1 | | | MAKEUP AIR TEMPERATURE. | | | | | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | | HVAC SYSTEM. | | | | | | | | | | | | CHRIS MONTELLO | | | 561-805-6733 | | | [email protected] | | | | | | |
|