Plan Review Notes
Plan Review Notes For Permit 17110283
Permit Number 17110283
Review Stop M
Sequence Number 3
Notes
Date Text
2018-11-08 11:19:362ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #17110283
 11/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1 - PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 2 - PROVIDE CUT SHEETS FOR COOKING APPLIANCES
  
 3 - BE ADVISED 2014 FLORIDA MECHANICAL CODE 508.1.1
 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]
  
  