Plan Review Notes
Plan Review Notes For Permit 17110283
Permit Number 17110283
Review Stop G
Sequence Number 3
Notes
Date Text
2018-11-27 12:42:433RD REVIEW: DENIED
 GAS COMMENTS
 REVIEWED PLAN SHEETS FG1.1, FG1.2 AND FG2.1
  
 AS DISCUSSED WITH SHAWNAKA VERMA, THE FOLLOWING
 COMMENTS APPLY.
  
 1. THIRD REQUEST; SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2
 2. THIRD REQUEST; SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE FBC-2014 FUEL GAS CODE SEC. 304.
  
 NEW COMMENT
  
 1. RE: PLAN SHEET FG1.1; CONCERNING THE EMERGENCY GAS
 SHUTOFF VALVE, VALVE SHALL SHUT OFF AUTOMATICALLY IN
 ACCORDANCE WITH NFPA 96, SECTION 10.4.1.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715