| 2018-05-02 12:13:51 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODE |
| | PERMIT #17110283 |
| | 5/2/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ENERGYGAUGE FORM: A) PROVIDE COMPLIANCE DATA FOR THE |
| | AC HEATING SYSTEMS SPECIFED AS 10 KW ON THE PLANS.. B) |
| | CORRECT THE COMPLIANCE DATA FOR SYSTEM 3 SPECIFYING THE |
| | COOLING SYSTEM AT 57 BTUH. |
| | |
| | 2) M-1: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE |
| | DETECTORS IN THE RETURN SYSTEMS OF THE AIR HANDLERS- |
| | SECTION 606.2.1. |
| | |
| | 3) M-1: PROVIDE AN AIR BALANCE CALCULATION THAT TAKES |
| | INTO ACCOUNT THE KITCHEN HOOD EXHAUST AND MAKEUP AIR |
| | CFMS, AND THE TOILET ROOM EXHAUST CFMS (NOTE- NO MAKEUP |
| | AIR SYSTEMS SHOWN FOR THE HOODS). PLEASE NOTE TWO HOODS |
| | ARE SHOWN ON THE PLAN- ONE RECIRCULATING AND ANOTHER |
| | THAT APPEARS TO BE A CONVENTIONAL HOOD. BOTH THESE |
| | HOODS ARE UNDER SEPARATE PERMIT HOWEVER |
| | |
| | PLEASE NOTE THAT THE RECIRCULATION HOOD SHALL BE UL |
| | 710B LISTED AND LABELED. CONCERNING THE SECOND HOOD, |
| | THE PLAN DOES NOT SHOW THE LOCATION OF THE HOOD EXHAUST |
| | WHICH NEEDS TO BE CLARIFIED. |
| | |
| | 4) M-1: SHOW THE O/A DUCT RUNS AN AIR INLET LOCATIONS- |
| | SECTION 401.4. INDICATE HOW THE OPENINGS WILL BE |
| | PROTECTED PER SECTION 401.5. |
| | |
| | 5) M-1: REFER TO SECTION C403.2.4.4 FBC-14 ENERGY |
| | CONSERVATION AND PROVIDE AUTOMATICALLY CONTROLLED |
| | SHUTOFF DAMPERS FOR THE O/A INTAKE DUCTS. |
| | |
| | 6) M-1: PROVIDE TOILET EXHAUST FAN SCHEDULES, AND SHOW |
| | THE EXHAUST DUCT RUNS AND DISCHARGE LOCATIONS- SECTION |
| | 501.3. |
| | |
| | 7) M-1: PROVIDE AN AIR DEVICE SCHEDULE. |
| | |
| | 8) M-1: SHOW THE LOCATION OF THE CONDENSERS AND THE |
| | REFRIGERANT PIPING RUNS. PLEASE INCLUDE THE TYPES AND |
| | SIZES OF REFRIGERANT PIPINGS, PIPING INSULATION, AND |
| | TOTAL RUN LENGTHS OF THE PIPING |
| | |
| | 9) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL |
| | GAS. |
| | |
| | 9) SUBMIT THE NOA FOR THE AC STANDS WITH APPROVAL STAMP |
| | BY THE EOR. |
| | |
| | 10) PLACE A CLEAR NOTE ON THE PLAN THAT INDICATES THE |
| | KITCHEN HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN |
| | COOLER WILL BE UNDER SEPARATE PERMIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |