Plan Review Notes
Plan Review Notes For Permit 17110283
Permit Number 17110283
Review Stop M
Sequence Number 2
Notes
Date Text
2018-05-02 12:13:511ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #17110283
 5/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGYGAUGE FORM: A) PROVIDE COMPLIANCE DATA FOR THE
 AC HEATING SYSTEMS SPECIFED AS 10 KW ON THE PLANS.. B)
 CORRECT THE COMPLIANCE DATA FOR SYSTEM 3 SPECIFYING THE
 COOLING SYSTEM AT 57 BTUH.
  
 2) M-1: SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE
 DETECTORS IN THE RETURN SYSTEMS OF THE AIR HANDLERS-
 SECTION 606.2.1.
  
 3) M-1: PROVIDE AN AIR BALANCE CALCULATION THAT TAKES
 INTO ACCOUNT THE KITCHEN HOOD EXHAUST AND MAKEUP AIR
 CFMS, AND THE TOILET ROOM EXHAUST CFMS (NOTE- NO MAKEUP
 AIR SYSTEMS SHOWN FOR THE HOODS). PLEASE NOTE TWO HOODS
 ARE SHOWN ON THE PLAN- ONE RECIRCULATING AND ANOTHER
 THAT APPEARS TO BE A CONVENTIONAL HOOD. BOTH THESE
 HOODS ARE UNDER SEPARATE PERMIT HOWEVER
  
 PLEASE NOTE THAT THE RECIRCULATION HOOD SHALL BE UL
 710B LISTED AND LABELED. CONCERNING THE SECOND HOOD,
 THE PLAN DOES NOT SHOW THE LOCATION OF THE HOOD EXHAUST
 WHICH NEEDS TO BE CLARIFIED.
  
 4) M-1: SHOW THE O/A DUCT RUNS AN AIR INLET LOCATIONS-
 SECTION 401.4. INDICATE HOW THE OPENINGS WILL BE
 PROTECTED PER SECTION 401.5.
  
 5) M-1: REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPERS FOR THE O/A INTAKE DUCTS.
  
 6) M-1: PROVIDE TOILET EXHAUST FAN SCHEDULES, AND SHOW
 THE EXHAUST DUCT RUNS AND DISCHARGE LOCATIONS- SECTION
 501.3.
  
 7) M-1: PROVIDE AN AIR DEVICE SCHEDULE.
  
 8) M-1: SHOW THE LOCATION OF THE CONDENSERS AND THE
 REFRIGERANT PIPING RUNS. PLEASE INCLUDE THE TYPES AND
 SIZES OF REFRIGERANT PIPINGS, PIPING INSULATION, AND
 TOTAL RUN LENGTHS OF THE PIPING
  
 9) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 9) SUBMIT THE NOA FOR THE AC STANDS WITH APPROVAL STAMP
 BY THE EOR.
  
 10) PLACE A CLEAR NOTE ON THE PLAN THAT INDICATES THE
 KITCHEN HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN
 COOLER WILL BE UNDER SEPARATE PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved