| 2018-05-04 11:32:27 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | |
| | 3. PROVIDE THE LONGEST RUN FROM THE METER TO THE |
| | FURTHEST APPLIANCE. PER THE FBC-2014 FUEL GAS APPENDIX |
| | A ? USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS |
| | CODE SEC. 402.4.1 |
| | |
| | 4. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP |
| | WITH 100' BASED ON THAT THE MANIFOLD SHALL BE 11/2" PER |
| | TABLE 402.4.2 SHOWN ON THE PLAN. |
| | |
| | 5. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP |
| | WITH 100' BASED ON THAT THE THE BRANCH FOR THE TANKLESS |
| | HEATER K5, K4 SHALL BE 11/4 PER TABLE 402.4.2 SHOWN ON |
| | THE PLAN. |
| | |
| | 6. I ADDED UP THE CUT LENGTHS ON THE RISERS AND CAME UP |
| | WITH 100' BASED ON THAT THE THE MANIFOLD K5, K4 SHALL |
| | BE 11/4 PER TABLE 402.4.2 SHOWN ON THE PLAN. |
| | |
| | 7. PROVIDE SIZE AND LENGTH OF VENT PIPING FOR TANKLESS |
| | HEATER. PER FBC-2014 FUEL GAS CODE SEC. 502 THRU 505. |
| | SHALL COMPLY WITH MANUFACTURE SPECIFICATIONS. |
| | |
| | 8. PROVIDE ELEVATION DRAWING SHOWING THE TERMINATION OF |
| | THE VENT FOR TANLESS WATER HEATER SHOW DISTANCE TO ANY |
| | OPENINGS IN THE BUILDING AND THE GROUND. PER FBC-2014 |
| | FUEL GAS CODE SEC. 502 THRU 505. SHALL COMPLY WITH |
| | MANUFACTURE SPECIFICATIONS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |