| 2018-05-05 08:17:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR 800 AMP SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD |
| | CALCULATION IS NOT ACCURATE FOR PANEL KX. FEEDERS MUST |
| | BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD AND 100% |
| | OF THE NON-CONTINUOUS LOAD. FACTORS IMPORTED FROM PANEL |
| | KA AND KB DO NOT INCLUDE THOSE DEMAND FACTORS.SHOW |
| | WINDOW LIGHTING IS NOT INCLUDED.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER NEC 210.62. |
| | (PER THIS CODE, AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED FOR EVERY 12 FEET OR MAJOR FRACTION THEREOF. |
| | THESE RECEPTACLES ALSO REQUIRE AUTOMATIC CONTROL PER |
| | ENERGY CODE AND THEY ARE CURRENTLY SHOWN TIED TO |
| | REGULAR RECEPTACLE CIRCUIT. PROVIDE CORRECTION.) |
| | 6. ALL RECEPTACLE OUTLETS IN KITCHEN AND BAR AREAS |
| | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | (NOT PROVIDED.) |
| | 7. PROVIDE DETAILS OF SHUTDOWN FOR ANY EQUIPMENT AND/OR |
| | RECEPTACLE OUTLETS LOCATED UNDER HOOD. NFPA 96, SECTION |
| | 10.4.1, FBC 107.2.1 (NOT PROVIDED) |
| | 8. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS |
| | ADEQUATE. NEC 110.10 (NOT PROVIDED) |
| | 9. CIRCUIT OR RECEPTACLE OUTLET FOR WATER FOUNTAIN |
| | REQUIRES GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8 |
| | (NOT PROVIDED) |
| | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | GENERATORS, COMMERCIAL HOOD SYSTEMS, SIGNS, SITE |
| | LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT |
| | INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A |
| | BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND |
| | DATA SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE |
| | SYSTEMS PRESENT. FBC 105.1, 107.2.1(NOT PROVIDED) |
| | |
| | NEW COMMENT: |
| | |
| | 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE |
| | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD |
| | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| | A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN |
| | REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |