2018-05-14 19:27:35SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 1) SHEET 100-A0.0 HEADING GOVERNING CODES:
  
 1A) ORIGINAL COMMENT:
 BUILDING CONSTRUCTION TYPE IS LISTED AS III-B
 SPRINKLERED. PLEASE NOTE THIS IS A 13 STORY HIGH RISE
 BUILDING. THE BUILDING CONSTRUCTION TYPE WOULD BE TYPE
 I-A. 2014 FBC-B TABLE 503.
  
 RESPONSE:
 SEMI-COMPLIED. CONSTRUCTION TYPE WAS REVISED TO I-A BUT
 IS MISSING THE SPRINKLER INFORMATION. THIS BUILDING IS
 REQUIRED TO BE SPRINKLERED. REVISE AS REQUIRED.
  
 2) COMPLIED.
  
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 4) ORIGINAL COMMENT:
 PLEASE NOTE ON SHEETS 110-A1.0 & 130-A1.2 THE LIFE
 SAFETY PLAN, BOTH PLANS SHOW ONLY ONE ACCESSIBLE SPACE
 AT A TABLE. PLEASE REFER TO THE 2014 FBC-ACCESSIBILITY
 CODE SECTION 226.1. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. 50X 0.05%=
 2.5 REQUIRED TO ROUND UP TO 3 SEATS.
  
 RESPONSE:
 REPEAT COMMENT. PLANS LAYOUT AND NUMBER OF PEOPLE WAS
 REVISED. NOW 72 SEATS ARE SHOWN. NOW NEEDS AT LEAST 4
 SEATS.
  
 5) ORIGINAL COMMENT:
 PLEASE SHOW THE ACCESSIBLE SEATS DISPERSED THROUGHOUT
 ALL CATEGORIES OF SEATING INCLUDING THE BAR AREA. 2014
 FBC-ACCESS. CODE SECTION 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 RESPONSE:
 REPEAT COMMENT. NEED TO DISPERSE SEATS THROUGHOUT ALL
 SEATING CATEGORIES, INCLUDING THE BOOTHS.
  
 6) SHOW COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2
 AND 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES
 INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH
 COUNTERS, AND BOOTHS.
  
 ORIGINAL COMMENT:
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 RESPONSE:
 REPEAT COMMENT. SHOW THE CLEAR FLOOR OR GROUND SPACE ON
 FLOOR PLAN FOR ALL DISPERSED ACCESSIBLE SEATS.
  
 ORIGINAL COMMENT:
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 RESPONSE:
 SEMI-COMPLIED. TABLE, BOOTH AND BAR DETAILS WERE
 PROVIDE ON SHEET 110-A1.0. NEED TO SHOW ACCESSIBLE
 BOOTH LOCATION ON FLOOR PLAN.
  
 7A) ORIGINAL COMMENT:
 SHEET 110-A1.0 IN THE UPPER LEFT HAND CORNER OF THE
 SHEET THERE IS A DOOR SCHEDULE AND DOOR D1 IN THE NOTES
 INDICATES SEE FLOOR PLAN A1.0. NEITHER DOOR IS
 IDENTIFIED ON THIS SHEET. D1 IS LABELED A 2 FOOT 10
 INCH DOOR. SEE SIZE OF DOORS IN THE 2014 FBC-B
 1008.1.1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL
 BE SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES (1.57 RAD).
  
 RESPONSE:
 SEMI-COMPLIED. THE WIND LOADS SPECIFIED FOR DOOR D3
 SEEM TO BE LOW. THIS BUILDING IS LOCATED IN EXPOSURE
 "D". REVISE AS REQUIRED OR PROVIDE ENGINEERED
 CALCULATIONS. SEC. 1609.4 FBC.
  
 7B) COMPLIED. DOOR D14 WAS DELETED.
  
 8) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NEW COMMENTS:
 10-LIFE SAFETY PLAN SHEET 130-A1.2:
 A) PLAN NEED TO SHOW THE REQUIRED ASSEMBLY AISLES AND
 DIMENSIONS (NON FIXED TABLES AREA AND BOOTHS AREA). SEE
 SEC. 1028.9 FBC. CROSSING THRU TABLES AND CHAIRS IS NOT
 ALLOWED FOR THE EGRESS PATH. (COORDINATE WITH SEATING
 AND TABLES SEC. 1028.10.1 FOR PROPER ARRANGEMENT OF OF
 DINING AREA AND REQUIRED AISLES).
 NOTE: ALSO CONSIDER THE MANEUVERING CLEARANCES REQUIRED
 AT THE EGRESS DOOR.
  
 B) EXIT TRAVEL DISTANCE IS MEASURED FROM THE MOST
 REMOTE POINT OF THE ROOM ALONG THE NATURAL AND
 UNOBSTRUCTED PATH TO THE EXIT. SEC. 1016.3 FBC. REVISE
 TRAVEL DISTANCE FROM KITCHEN STORAGE ROOM, FREEZER
 REACH-IN AREA, PIZZA PREP AND BAR AREA. ALSO, REVISE
 OVERALL DISTANCES. COORDINATE WITH ITEM #10A) ABOVE.
  
 C) NUMBER OF PEOPLE SHOWN ON THE 6'-0" LONG BOOTHS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 1004.4 FBC.
  
 D) REVISED OCCUPANT LOAD ON SHEET 100-A0.0 SPECIFIES 73
 SEATS. LIFE SAFETY PLAN SHOWS 72. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) SCOPE OF WORK ON SHEET 100-A0.0 SPECIFIES BUILT OUT
 TO INCLUDE PAIR OF ENTRY DOORS. DOOR SCHEDULE ON SHEET
 110-A1.0 DOESN'T PROVIDE SPECIFICATIONS FOR THE ENTRY
 DOORS. PROVIDE COMPLETE INFORMATION. ALSO, SPECIFY THE
 PANIC HARDWARE. SEC. 1008.1 FBC.
 NOTE: STOREFRONT PERMIT #18020691 ONLY SHOWS ONE ENTRY
 DOOR.
  
 F) SECOND EXIT DOOR BY THE PARKING GARAGE SIDE IS USING
 THE RAMP AS PART OF A MEANS OF EGRESS. THIS RAMP SHALL
 COMPLY WITH SEC. 1010 FBC. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE RAMP COMPLIES WITH THIS
 SECTION. SHOW COMPLIANCE WITH ALL REQUIREMENTS
 INCLUDING SLOPE, CROSS SLOPE, VERTICAL RISE, LANDINGS,
 , HANDRAILS, ETC.
  
  
 11- BASED ON THE LAYOUT OF NON FIXED TABLES AND CHAIRS
 IT LOOKS LIKE THERE IS NOT AN ACCESSIBLE ROUTE TO THE
 RESTROOMS . SEC. 202.4 FBC-ACCESSIBILITY. REVISE AS
 REQUIRED TO PROVIDE THE ACCESSIBLE ROUTE. COORDINATE
 WITH ITEM #10A) ABOVE.
  
 12-VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 13- CODE CLASSIFICATIONS TABLE ON SHEET 100-A0.0:
 A) THE KITCHEN AREA NUMBER OF OCCUPANTS IS BASED ON THE
 GROSS AREA NOT NET AREA. REVISE AS REQUIRED BY TABLE
 1004.1.2 FBC.
 NOTE: CLARIFY NUMBER OF EMPLOYEES. ONLY 5 EMPLOYEES FOR
 ENTIRE ASSEMBLY?
  
 B) PROVIDE SEPARATE OCCUPANT LOAD FOR THE FIXED SEATS
 (BOOTHS, BAR STOOLS) AND FOR NON FIXED SEATS AS
 REQUIRED BY SEC. 1004.4 FBC.
  
 C) CLEARLY SPECIFY THE MAXIMUM OCCUPANT LOAD. SEC.
 1004.3 FBC.
  
 D) REVISE THE EXIT WIDTH INFORMATION ON THE CODE
 CLASSIFICATION TABLE. SEE SEC. 1008.1.1 AND SEC. 1005.3
 FBC. THE INCHES PROVIDED IS INCORRECT. SEE NUMBER AND
 SIZE OF DOORS PROVIDED AND REVISE AS REQUIRED. SEE SEC.
 1008.1.1 FOR CORRECT WAY TO DETERMINE THE DOOR CLEAR
 OPENING.
  
  E) LEFT HAND SIDE COLUMN OF THE CODE CLASSIFICATION
 TABLE IS CALLING FOR BUSINESS OCCUPANCY. THIS IS
 ASSEMBLY A-2. REVISE AS REQUIRED. SEC. 303.3 FBC.
  
 14- CLARIFY WHAT IS THE HATCHED PARTITION SHOWN IN ALL
 PLANS BY THE ACCESSIBLE RESTROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 15- SHEET 110-A1.0:
 A) PROVIDE COMPLETE FRAMING DETAIL AND SPECIFICATIONS
 FOR THE NEW SINGLE FIRE RATED EXIT DOOR ON THE EXISTING
 FIRE RATED WALL. SEC. 701.1 FB AND SEC. 1609.1 FBC.
  
 B) RESTROOM GRAB BARS NEED TO BE MEASURED TO THE TOP OF
 THE GRIPPING SURFACE NOT THE CENTER LINE. REVISE AS
 REQUIRED. SEC. 609.4 FBC ACCESSIBILITY.
  
  C) PROVIDE DETAILS AND SPECIFICATIONS FOR THE SERVICE
 COUNTER BY THE PIZZA PREP AREA SHOWING COMPLIANCE WITH
 SEC. 227.3 FBC ACCESSIBILITY.
  
 16- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) NEW FIRE RATED EXIT DOOR.
  
  B) NEW DOUBLE ENTRY DOORS. (NOTE: COORDINATE WITH
 STOREFRONT PERMIT)
  
  17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  