| 2017-11-29 09:08:11 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. ACCESSIBILITY PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING: FBC ACC |
| | |
| | 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE.VERTICAL GRAB BARS ARE NOT APPROVED. |
| | |
| | 604.5.1 SIDE WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND |
| | EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. |
| | |
| | 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| | OTHER SIDE. |
| | |
| | 604.2 LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, |
| | |
| | 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THIS IS |
| | UNCLEAR ON THE PLAN |
| | |
| | 2. SHT. 110-A1.0 ON THE FLOOR PLAN IT APPEARS THE CLEAR |
| | FLOOR SPACE FOR THE WATER CLOSET IN WOMENS BATHROOM IS |
| | ENCROACHING OVER INTO THE KITCHEN WHERE THE 3 COMP SINK |
| | IS LOCATED PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE LABEL THE CLEAR FLOOR SPACE IN BATHROOMS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT 120-A1.1 ON THE ENLARGED KITCHEN PLAN THE ICE |
| | CUBER B4 IS NOT LABELED PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 5. SHT. 120-A1.1 K10 IS THE HOT FOOD TABLE ELECTRIC OR |
| | GAS IT DOES NOT INDICATE ON THE EQUIPMENT SCHEDULE |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT. 120-A1.1 K21 IS NOT LISTED ON THE EQUIPMENT |
| | SCHEDULE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. 190-P1.0 ON THE WATER ISOMETRIC THE AIR |
| | CHAMBERS ARE NOT APPROVED THEY SHALL COMPLY WITH FBC PL |
| | 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | 8. SHT. 190-P1.0 ON THE WATER ISOMETRIC IT SHOWS THE |
| | TANKLESS WATER HEATER ABOVE THE MOP AND HAND SINK ON |
| | THE FLOOR PLAN IT SHOWS ABOVE THE 3 COMP SINK PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHT. 190-P1.0 ON THE WATER ISOMETRIC PLEASE SHOW |
| | SIZE OF ALL DROPS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT. 190-P1.0 ON THE WATER ISOMETRIC VALVES ARE |
| | REQUIRED AT EACH DROP AND THE MAIN FEED COMING INTO THE |
| | BUILDING .PER FBC PL 606.1 LOCATION OF FULL-OPEN |
| | VALVES. |
| | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: 2. ON THE WATER DISTRIBUTION SUPPLY PIPE AT |
| | THE ENTRANCE INTO THE STRUCTURE. 5. ON THE TOP OF EVERY |
| | WATER DOWN-FEED PIPE IN OCCUPANCIES OTHER THAN ONE- AND |
| | TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | 11. SHT. 190-P1.0 ON THE WATER ISOMETRIC A BACK FLOW IS |
| | REQUIRED ON THE SUPPLY FOR ICE MACHINES, BEVERAGE |
| | DISPENSERS AND WATER FILTERS. PER FBC PL 608.3, |
| | 608.16.1 AND 608.16.10 |
| | |
| | 12. SHT. 190-P1.0 THE NOTE UNDER PLUMBING GENERAL NOTES |
| | STATES THE GREASE WASTE PIPE SHALL BE CPVC BUT THE |
| | ISOMETRIC SHOWS THE BRANCH PIPING AS PVC PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 13. THE 3 COMP SINK SHALL BE INDIRECTLY WASTED TO FLOOR |
| | SINK. PER FBC PL 802.1.1 |
| | |
| | 14. THE BRANCH DRAIN FOR THE DRINKING FOUNTAIN SHALL |
| | CONNECT TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM |
| | GROUPS. PER FBC PL 912.1 |
| | |
| | 15. THE GLASS WASHER IN BAR AREA, THE FLOOR DRAINS IN |
| | THE BATHROOMS AND DRAINS FROM THE ICE MACHINES SHALL |
| | NOT DISCHARGE INTO THE GREASY WASTE SYSTEM. PER FBC PL |
| | 1003.2 |
| | |
| | 16. PLEASE PROVIDE SPECIFICATIONS FOR THE GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. PLEASE PROVIDE A PIPING DETAIL FOR GREASE |
| | INTERCEPTOR SHOWING TWO WAY CLEANOUTS ON INLET AND |
| | OUTLET ALSO TEST PORT ON OUTLET. PER WPB UTILITIES DEPT |
| | |
| | 18. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. PER FBC PL 1003.2 |
| | |
| | 19. SHT. 210-P2.1 DETAIL A1 SHOWS A 2" WATER MAIN |
| | BREAKING DOWN TO 11/2" THE WATER ISOMETRIC ON SHT-P1.0 |
| | ONLY SHOWS A 3/4" MAIN PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 20. IF A WATER FILTER SYSTEM IS BEING USED PLEASE SHOW |
| | ON WATER ISOMETRIC AND PROVIDE A PIPING DETAIL. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |