Plan Review Notes
Plan Review Notes For Permit 17110283
Permit Number 17110283
Review Stop G
Sequence Number 1
Notes
Date Text
2017-11-29 07:49:491ST REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 (1). SHT. 200-P2.0 GAS SUPPLY DIAGRAM KEYNOTES
 A) # 109 DIRT LEGS SHALL BE LOCATED UPSTREAM OF
 APPLIANCES WHERE THE PIPING GOES FROM VERTICAL TO
 HORIZONTAL. PER FBC FG 408.4
 B) # 111 ALL BRANCHES INCLUDING FUTURE SHALL BE LABELED
 WITH SIZE, TYPE OF PIPE, LENGTH AND BTU LOAD. PER FBC
 FG 402
 C) #112 THE COMPLETE SYSTEM SHALL BE LABELED WITH SIZE
 OF PIP, TYPE OF PIPE, LENGTH OF EACH SECTION AND BTU
 LOAD BEFORE IT CAN BE APPROVED. IF A COMPLETED SYSTEM
 CAN NOT BE COMPLETED PLEASE REMOVE FROM PLAN AND SUBMIT
 UNDER THE SEPARATE GAS PERMIT AND PLANS OTHERWISE IT
 MIGHT HOLD UP APPROVAL OF THE MASTER PERMIT.
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION GUIDES FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 402.2
  
 10. PLEASE SUBMIT SIZING TABLES FROM FBC FG CODE USED
 TO SIZE SYSTEM. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  